Products Solutions Services
Operating Instructions
Liquisys M CCM223/253
Transmitter for free chlorine, chlorine dioxide and total
chlorine
BA00214C/07/EN/15.15
71300499
Liquisys M CCM223/253 Table of contents
Endress+Hauser 3
Table of contents
1 Document information .............. 5
1.1 Warnings ............................ 5
1.2 Symbols used .......................... 5
1.3 Symbols on the device ................... 5
1.4 Electrical symbols ...................... 6
2 Basic safety instructions ............ 7
2.1 Requirements for personnel ............... 7
2.2 Designated use ........................ 7
2.3 Occupational safety ..................... 7
2.4 Operational safety ...................... 8
2.5 Product safety ......................... 8
2.5.1 State of the art .................. 8
2.5.2 IT security ...................... 8
3 Incoming acceptance and product
identification ....................... 9
3.1 Incoming acceptance .................... 9
3.2 Scope of delivery ....................... 9
3.3 Product identification ................... 10
3.3.1 Nameplate .................... 10
3.3.2 Product identification ............ 10
3.4 Certificates and approvals ............... 10
3.4.1  mark ...................... 10
3.4.2 CSA General Purpose ............. 10
4 Installation ....................... 11
4.1 Installation at a glance .................. 11
4.1.1 Measuring system ............... 12
4.2 Installation conditions .................. 14
4.2.1 Field device .................... 14
4.2.2 Panel-mounted device ............ 15
4.3 Installation instructions ................. 16
4.3.1 Field device .................... 16
4.3.2 Panel-mounted device ............ 18
4.4 Post-installation check .................. 18
5 Electrical connection .............. 19
5.1 Wiring ............................. 19
5.2 Electrical connection, version 1 ........... 19
5.3 Electrical connection, version 2 ........... 21
5.4 Device connection ..................... 22
5.5 Measuring cables and sensor connection .... 24
5.6 Three-point step controller for Cl
2
/ ClO
2
/
total chlorine ......................... 28
5.7 Alarm contact ........................ 29
5.8 Post-connection check .................. 29
6 Operation options ................. 30
6.1 Quick operation guide .................. 30
6.2 Display and operating elements ........... 30
6.2.1 Display ....................... 30
6.2.2 Operating elements .............. 32
6.2.3 Key functions .................. 32
6.3 Local operation ....................... 35
6.3.1 Automatic/manual mode .......... 35
6.3.2 Operating concept ............... 36
7 Commissioning .................... 38
7.1 Function check ....................... 38
7.2 Switching on ......................... 38
7.3 Quick Setup .......................... 40
7.4 Device configuration ................... 42
7.4.1 Setup 1 (chlorine/chlorine dioxide) .. 42
7.4.2 Setup 2 (temperature or pH/ORP) ... 44
7.4.3 Current input .................. 47
7.4.4 Current outputs ................. 51
7.4.5 Alarm ........................ 55
7.4.6 Check ........................ 56
7.4.7 Relay configuration .............. 60
7.4.8 Service ....................... 77
7.4.9 E+H Service .................... 79
7.4.10 Interfaces ..................... 80
7.4.11 Communication ................. 80
7.5 Calibration .......................... 81
8 Diagnostics and troubleshooting ... 85
8.1 Trouble shooting instructions ............. 85
8.2 System error messages .................. 85
8.3 Process-specific errors .................. 89
8.4 Device-specific errors ................... 93
9 Maintenance ...................... 95
9.1 Maintenance of the entire measuring point .. 95
9.1.1 Cleaning the transmitter .......... 95
9.1.2 Cleaning the pH/mV sensors
(EP version) ................... 96
9.1.3 Maintenance of chlorine sensors .... 97
9.1.4 Assembly ..................... 97
9.1.5 Maintenance of pH connecting
cables and junction boxes (EP
version) ...................... 98
9.2 Test and simulation .................... 98
9.2.1 Chlorine sensors ................ 98
9.2.2 Temperature measurement ........ 99
9.2.3 pH/ORP measurement ............ 99
9.2.4 Flow monitoring ................ 99
10 Repair ........................... 101
10.1 Spare parts ......................... 101
10.2 Disassembling the panel-mounted device ... 101
10.3 Disassembling the field device ........... 104
10.4 Replacing the central module ............ 107
Table of contents Liquisys M CCM223/253
4 Endress+Hauser
10.5 Return ............................. 107
10.6 Disposal ........................... 108
11 Accessories ...................... 109
11.1 Sensors ............................ 109
11.2 Connection accessories ................. 109
11.3 Installation accessories ................ 110
11.4 Software and hardware add-ons .......... 111
11.5 Metering system ..................... 111
11.6 Calibration accessories ................. 112
12 Technical data ................... 113
12.1 Input .............................. 113
12.2 Output ............................ 113
12.3 Power supply ........................ 116
12.4 Performance characteristics ............. 117
12.5 Environment ........................ 117
12.6 Mechanical construction ............... 118
13 Appendix ........................ 119
Index ................................. 130
Liquisys M CCM223/253 Document information
Endress+Hauser 5
1 Document information
1.1 Warnings
Structure of information Meaning
L
DANGER
Causes (/consequences)
Consequences of non-compliance
(if applicable)
Corrective action
This symbol alerts you to a dangerous situation.
Failure to avoid the dangerous situation will result in a fatal or serious
injury.
L
WARNING
Causes (/consequences)
Consequences of non-compliance
(if applicable)
Corrective action
This symbol alerts you to a dangerous situation.
Failure to avoid the dangerous situation can result in a fatal or serious
injury.
L
CAUTION
Causes (/consequences)
Consequences of non-compliance
(if applicable)
Corrective action
This symbol alerts you to a dangerous situation.
Failure to avoid this situation can result in minor or more serious injuries.
NOTICE
Cause/situation
Consequences of non-compliance
(if applicable)
Action/note
This symbol alerts you to situations which may result in damage to
property.
1.2 Symbols used
Additional information, tips
Permitted or recommended
Forbidden or not recommended
1.3 Symbols on the device
Symbol Meaning
Reference to device documentation
Document information Liquisys M CCM223/253
6 Endress+Hauser
1.4 Electrical symbols
Symbol Meaning
A0027423
Direct current
A terminal at which DC is present or through which DC flows.
A0027424
Alternating current
A terminal to which alternating voltage (sine-wave) is applied or through
which alternating current flows.
A0027425
Direct current or alternating current
A terminal at which direct voltage or alternating voltage is present or
through which direct current or alternating current flows.
A0027426
Ground connection
A terminal which, from the user's point of view, is already grounded via a
grounding system.
A0027427
Protective ground connection
A terminal which must be connected to ground prior to establishing any
other connections.
A0019929
Class II equipment
Reinforced or double insulation
A0027420
Alarm relay
A0027428
Input
A0027429
Output
A0027430
DC voltage source
A0027431
Temperature sensor
Liquisys M CCM223/253 Basic safety instructions
Endress+Hauser 7
2 Basic safety instructions
2.1 Requirements for personnel
Installation, commissioning, operation and maintenance of the measuring system may
be carried out only by specially trained technical personnel.
The technical personnel must be authorized by the plant operator to carry out the
specified activities.
The electrical connection may be performed only by an electrical technician.
The technical personnel must have read and understood these Operating Instructions
and must follow the instructions contained therein.
Measuring point faults may be repaired only by authorized and specially trained
personnel.
Repairs not described in the Operating Instructions provided may only be carried out
directly by the manufacturer or by the service organization.
2.2 Designated use
Liquisys M CCM223/253 is a transmitter for determining the amount of free chlorine,
chlorine dioxide or total chlorine dissolved in water.
The transmitter is particularly suited for use in the following areas:
Drinking water
Water treatment
Cooling water
Gas scrubbers
Reverse osmosis
Food processing
Swimming pool and bathing pool water
Use of the device for any purpose other than that described, poses a threat to the safety of
people and of the entire measuring system and is therefore not permitted.
The manufacturer is not liable for damage caused by improper or non-designated use.
2.3 Occupational safety
As the user, you are responsible for complying with the following safety conditions:
Installation guidelines
Local standards and regulations
Electromagnetic compatibility
The product has been tested for electromagnetic compatibility in accordance with the
applicable European standards for industrial applications.
The electromagnetic compatibility indicated applies only to a product that has been
connected in accordance with these Operating Instructions.
Basic safety instructions Liquisys M CCM223/253
8 Endress+Hauser
2.4 Operational safety
1. Before commissioning the entire measuring point, verify that all connections are
correct. Ensure that electrical cables and hose connections are undamaged.
2. Do not operate damaged products, and safeguard them to ensure that they are not
operated inadvertently. Label the damaged product as defective.
3. If faults cannot be rectified:
Take the products out of operation and safeguard them to ensure that they are not
operated inadvertently.
2.5 Product safety
2.5.1 State of the art
The product is designed to meet state-of-the-art safety requirements, has been tested, and
left the factory in a condition in which it is safe to operate. The relevant regulations and
European standards have been observed.
2.5.2 IT security
We only provide a warranty if the device is installed and used as described in the
Operating Instructions. The device is equipped with security mechanisms to protect it
against any inadvertent changes to the device settings.
IT security measures in line with operators' security standards and designed to provide
additional protection for the device and device data transfer must be implemented by the
operators themselves.
Liquisys M CCM223/253 Incoming acceptance and product identification
Endress+Hauser 9
3 Incoming acceptance and product
identification
3.1 Incoming acceptance
1. Verify that the packaging is undamaged.
Notify your supplier of any damage to the packaging.
Keep the damaged packaging until the matter has been settled.
2. Verify that the contents are undamaged.
Notify your supplier of any damage to the delivery contents.
Keep the damaged products until the matter has been settled.
3. Check the delivery for completeness.
Check it against the delivery papers and your order.
4. Pack the product for storage and transportation in such a way that it is protected
against impact and moisture.
The original packaging offers the best protection.
The permitted ambient conditions must be observed (see "Technical data").
If you have any questions, please contact your supplier or your local sales center.
3.2 Scope of delivery
The delivery of the field device comprises:
1 transmitter
1 plug-in screw terminal, 3-pin
1 cable gland Pg 7
1 cable gland Pg 16 reduced
2 cable glands Pg 13.5
1 set of Operating Instructions
For versions with HART communication:
1 set of Operating Instructions: Field communication with HART
For versions with PROFIBUS interface:
1 set of Operating Instructions: Field communication with PROFIBUS PA/DP
The delivery of the panel-mounted device comprises:
1 transmitter
1 set of plug-in screw terminals
2 tensioning screws
Also for EP version: 1 BNC connector (solder-free)
1 set of Operating Instructions
For versions with HART communication:
1 set of Operating Instructions: Field communication with HART
For versions with PROFIBUS interface:
1 set of Operating Instructions: Field communication with PROFIBUS PA/DP
Incoming acceptance and product identification Liquisys M CCM223/253
10 Endress+Hauser
3.3 Product identification
3.3.1 Nameplate
The nameplate provides you with the following information on your device:
Manufacturer identification
Order code
Extended order code
Serial number
Ambient and process conditions
Input and output values
Safety information and warnings
Compare the data on the nameplate with your order.
3.3.2 Product identification
The order code and serial number of your product can be found in the following locations:
On the nameplate
In the delivery papers
Obtaining information on the product
1. Go to the product page for your product on the Internet.
2. In the navigation area on the right-hand side, select "Check your device features"
under "Device support".
An additional window opens.
3. Enter the order code from the nameplate into the search field.
You will receive information on each feature (selected option) of the order code.
3.4 Certificates and approvals
3.4.1  mark
The product meets the requirements of the harmonized European standards. As such, it
complies with the legal specifications of the EC directives. The manufacturer confirms
successful testing of the product by affixing to it the mark.
3.4.2 CSA General Purpose
The following device versions meet the requirements of CSA and ANSI/UL for Canada and
the US:
CCM253-**2/3/7***
CCM223-**2/3/7***
Liquisys M CCM223/253 Installation
Endress+Hauser 11
4 Installation
4.1 Installation at a glance
Proceed as follows to completely install the measuring point:
Install the transmitter (see the "Installation instructions" section).
If the sensor is not yet installed in the measuring point, install it (see Technical
Information of the sensor).
Connect the sensor to the transmitter as illustrated in the "Electrical connection" section.
Connect the transmitter as illustrated in the "Electrical connection" section.
Commission the transmitter as explained in the "Commissioning" section.
Installation Liquisys M CCM223/253
12 Endress+Hauser
4.1.1 Measuring system
Version 1: free chlorine and chlorine dioxide
A complete measuring system comprises:
Transmitter Liquisys M CCM223 or CCM253
A membrane covered sensor CCS140/141 for Cl
2
or CCS240/241 for ClO
2
an open
sensor 963 for Cl
2
Flow assembly CCA250 (not required for sensor 963)
Optionally:
pH or ORP electrode
Proximity switch INS for flow monitoring (not with sensor 963)
Extension cable CMK for chlorine measurement
Extension cable CYK71 for pH/ORP measurement
An extension cable MK for proximity switch INS
Junction box VBC
1
2
3
4
5
6
7
8
9
A0024088
 1 Measuring system for the measurement of free chlorine or chlorine dioxide in flow operation (example)
1 Flow assembly CCA250
2 Medium inflow
3 Proximity switch INS
4 Mounting location for pH/ORP sensors
5 Chlorine sensor
6 Medium outlet
7 Sampling tap
8 Measuring cable
9 Transmitter CCM253
Version 2: total chlorine
A complete measuring system comprises:
Transmitter Liquisys M CCM223 or CCM253
Total chlorine sensor CCS120
Flow assembly CCA250 or immersion assembly CYA611
Measuring cable CPK9 with internal PML
Liquisys M CCM223/253 Installation
Endress+Hauser 13
Optionally:
pH or ORP electrode
Proximity switch INS for flow monitoring (only with flow assembly)
Extension cable CPK9 with internal PML for chlorine measurement
Extension cable CYK71 for pH/ORP measurement
An extension cable MK for proximity switch INS
Junction box VBC
Weather protection cover CYY101 for field housing
1
2
4
5
3
6
A0024089
 2 Measuring system for the measurement of total chlorine in immersion operation (example)
1 Junction box
2 Transmitter CCM253
3 Measuring cable
4 Immersion assembly CYA611
5 Chlorine sensor CCS120
6 Assembly adapter G1
Installation Liquisys M CCM223/253
14 Endress+Hauser
4.2 Installation conditions
4.2.1 Field device
Pg 7
Pg 16
M 5
11 (0.43)
Ø 6 (0.24)
115 (4.53)
157 (6.18)
247 (9.72)
70 (2.76)
70 (2.76)
154 (6.06)
170 (6.69)
Pg 13.5
A0024637
 3 Field device, dimensions in mm (inch)
There is a hole in the perforation for the cable entry (connection of supply voltage). It
serves as a pressure balance during air shipment. Make sure no moisture penetrates
the inside of the housing before the cable installation. The housing is completely air-
tight after cable installation.
Liquisys M CCM223/253 Installation
Endress+Hauser 15
1
2
3
4
A0024640
 4 View into the field housing
1 Removable electronics box
2 Terminals
3 Partition plate
4 Fuse
4.2.2 Panel-mounted device
90 (3.54)
139 (5.47)
96 (3.78)
6 (0.24)
92 (3.62)
149.5 (5.89)
A0024641
 5 Panel-mounted device, dimensions in mm (inch)
Installation Liquisys M CCM223/253
16 Endress+Hauser
4.3 Installation instructions
4.3.1 Field device
There are several ways of securing the field housing:
Wall mounting with fixing screws
Post mounting to cylindrical pipes
Post mounting to a square securing mast
NOTICE
Effect of climatic conditions (rain, snow, direct sunlight etc.)
Impaired operation to complete transmitter failure
When installing outside, always use the weather protection cover (accessory).
Transmitter wall mounting
1
2
154 (6.06)
Ø 6 (0.24)
A0024638
 6 Field device wall mounting
1 Fixing bore holes
2 Plastic caps
Proceed as follows to mount the transmitter on the wall:
Create the bore holes as shown in →  6.
Drive two fixing screws through the fixing bore holes (1) from the front.
Mount the transmitter on the wall as shown.
Cover the bores with plastic caps (2).
Transmitter post mounting
You require a post mounting kit to secure the field device to horizontal and vertical
posts or pipes (max. Ø 60 mm (2.36")). This can be acquired as an accessory (see the
"Accessories" section).
Liquisys M CCM223/253 Installation
Endress+Hauser 17
1
2
3
1
1
3
Ø max. 60 (2.36)
A0024635
 7 Field device on horizontal or vertical pipes
1 Securing screws
2 Fixing screws
3 Securing plate
Proceed as follows to mount the transmitter on a post:
1. Guide the two securing screws (1) of the mounting kit through the openings on the
securing plate (3).
2. Screw the securing plate onto the transmitter using the four fixing screws (2).
3. Secure the bracket with the field device on the post or pipe using the clip.
You can also secure the field device to the Flexdip CYH112 bracket in conjunction with the
weather protection cover. These can be acquired as accessories, see the "Accessories"
section.
A0027433
 8 Field device on Flexdip CYH112 bracket with weather protection cover
Installation Liquisys M CCM223/253
18 Endress+Hauser
4.3.2 Panel-mounted device
The panel-mounted device is secured with the tensioning screws supplied →  9
The necessary installation depth is approx. 165 mm (6.50").
A0024639
 9 Dimensions in mm (inch)
1 Mounting plate
2 Seal
3 Tensioning screws
* Necessary installation depth
4.4 Post-installation check
After installation, check the transmitter for damage.
Check whether the transmitter is protected against moisture and direct sunlight (e.g. by
the weather protection cover).
Liquisys M CCM223/253 Electrical connection
Endress+Hauser 19
5 Electrical connection
L
WARNING
Device is live
Incorrect connection may result in injury or death.
The electrical connection may be performed only by an electrical technician.
The electrical technician must have read and understood these Operating Instructions
and must follow the instructions contained therein.
Prior to commencing connection work, ensure that no voltage is present on any cable.
5.1 Wiring
L
WARNING
Risk of electric shock!
At the supply point, the power supply must be isolated from dangerous live cables by
double or reinforced insulation in the case of devices with a 24 V power supply.
NOTICE
The device does not have a power switch
The customer must provide a protected circuit breaker in the vicinity of the device.
The circuit breaker must be a switch or power switch, and you must label it as the
circuit breaker for the device.
The electrical connection of the transmitter depends on the sensor:
If you are using the membrane-covered sensor CCS140 / 141 / 240 / 241 or the open
sensor 963, follow the instructions and illustrations in the "Electrical connection, version
1" section.
If you are using the total chlorine sensor CCS120, follow the instructions and
illustrations in the "Electrical connection, version 2" section.
5.2 Electrical connection, version 1
The wiring diagram shows the connections of a device equipped with all the options. The
connection of the sensors to the various measuring cables is explained in more detail in
the "Measuring cables and sensor connection" section.
Electrical connection Liquisys M CCM223/253
20 Endress+Hauser
15 V
85
86
81
93
82
94
mA
31
32
mA
mA
33
34
54
55
56
23
24
90
12
11
91
92
S
ClO
2
ClO
2
Cl
2
Cl
2
K
A
A
K
K
A
NTC
pH
Red.
Ref.
PA/
PM
10–50 V
41
42
43
47
48
49
57
58
59
51
52
53
L+
L–N
L1
~ =
pH/
Redox
GN
BN
RD
BU
RD
BK
BN
BU
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
*
A0001903
 10 Electrical connection of the transmitter (version 1)
A pH/ORP input (optional) I Auxiliary voltage output
B Sensor CCS140/141/240/241 J Alarm (current-free contact position)
C Sensor 963 (alternative) K Relay 1 (current-free contact position)
D Signal output 1, chlorine / chlorine dioxide L Relay 2 (current-free contact position)
E Signal output 2, temperature, pH or ORP M Relay 3 (current-free contact position)
F Binary input 1 (hold/cleaning) N Relay 4 (current-free contact position)
G Proximity switch INS O Current input 4 to 20 mA
H Binary input 2 P Power connection
* Auxiliary voltage of terminal 85/86 can be used
The device is approved for protection class II and is generally operated without a
protective ground connection. Circuits "E" and "I" are not galvanically isolated from each
other.
Liquisys M CCM223/253 Electrical connection
Endress+Hauser 21
5.3 Electrical connection, version 2
The wiring diagram shows the connections of a device equipped with all the options. The
connection of the sensors to the various measuring cables is explained in more detail in
the "Measuring cables and sensor connection" section.
15 V
85
86
81
93
82
94
mA
31
32
mA
mA
33
34
54
55
56
23
24
90
12
11
S
ClO
2
ClO
2
Cl
2
Cl
2
pH
Red.
Ref.
PA/
PM
10–50 V
41
42
43
47
48
49
57
58
59
51
52
53
L+
L–N
L1
~ =
pH/
Redox
YE
BK
BK
BN
BU
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
15 V
85
86
CCS
120
WH
GN
BN
C
*
A0001904
 11 Electrical connection of the transmitter (version 2)
A pH/ORP input (optional) * Auxiliary voltage of terminal 85/86 can be used
B Sensor CCS120 J Alarm (current-free contact position)
C Auxiliary voltage output K Relay 1 (current-free contact position)
D Signal output 1, total chlorine L Relay 2 (current-free contact position)
E Signal output 2, temperature, pH or ORP M Relay 3 (current-free contact position)
F Binary input 1 (hold/cleaning) N Relay 4 (current-free contact position)
Electrical connection Liquisys M CCM223/253
22 Endress+Hauser
G Proximity switch INS O Current input 4 to 20 mA
H Binary input 2 P Power connection
The device is approved for protection class II and is generally operated without a
protective ground connection. Circuits "E" and "C" are not galvanically isolated from
each other.
5.4 Device connection
Field device connection
Proceed as follows to connect the field device:
1. Open the housing cover to access the terminal block in the connection compartment.
2. Break through the perforation for a cable gland, mount a Pg gland and guide the
cable through this Pg gland.
3. Connect the cable in accordance with the terminal assignment.
4. Tighten the Pg gland again.
NOTICE
Non-observance could cause incorrect measurement.
Make absolutely sure to protect the cable ends and terminals from moisture.
Terminals marked NC may not be connected.
Unmarked terminals may not be connected.
pH / Redox
42
+
+
++++ -
-
----
434154 55 56
NC
91
90
31
11
12
32
92
PA/PM
3433
S
REF
NC 938685 94 81
23
82
24
NC
51 52 53 57 58 59 47 48 49
Cl
ClO
2
(963:92/K)
2
Temp.
pH/Redox
(opt.)
+15V
10mA
BN
(RD)GN(BU)
BN
REL 4SENSOR REL 3 REL 2 REL 1
131194-4D
CCM 253
Digital 2
(INS)
Digital 1
4..20mA
1191/A
1290/K
NC
Mains
Hilfsenergie
L1
+
N
-
(AC)
(DC)
Contacts:
max. 2A
AC: 250V/500VA
DC: 30V/60W
A0002276
 12 Field device connection compartment sticker
Please label the sensor terminal block with the sticker provided.
Panel-mounted device connection
To connect the panel-mounted device, connect the cables in accordance with the terminal
assignment to the terminals on the rear of the device.
Liquisys M CCM223/253 Electrical connection
Endress+Hauser 23
REL1
REL2
REL3
REL4
4..20mA
24
23
49
COM
COM
COM
COM
-
+
59
54
55
56
52
51
53
58
57
48
47
131084-4C
31 +
32 -
33 +
PA/PM
34 -
85 +
NC
91
90
NC
(REF)
Sensor
NC
86 -
93 + S
94 - 42
81 + 43
82 - 41
Cl
2
Temp.
pH
Redox
(opt.)
+15V
10mA
Digital 2
(INS)
Digital 1
92
12
11
K
A
BN
BN
GN
131192-4C
K
ClO
2
963
CCS..
963
BNC: pH/Redox + REF
RD
BU
Mains
Contacts: max. 2A, AC:250V/500VA, DC:30V/60W
L1 +
AC DC
N -
A0002277
 13 Panel-mounted device connection sticker
NOTICE
Non-observance could cause incorrect measurement.
Make absolutely sure to protect the cable ends and terminals from moisture.
Terminals marked NC may not be connected.
Unmarked terminals may not be connected.
Please label the sensor terminal block with the sticker provided.
Electrical connection Liquisys M CCM223/253
24 Endress+Hauser
5.5 Measuring cables and sensor connection
Sensor type Cable Extension
Chlorine/chlorine dioxide sensors
CCS140 / 141 / 240 / 241
3 m (9.8 ft) CMK, permanently connected VBC box + CMK
Chlorine sensor 963 - VBC box + MK
Temperature sensor for chlorine sensor 963 CPK1
Total chlorine sensor CCS120 CPK9-N*A1B VBC box + CYK71
pH or ORP sensor without temperature
sensor
CPK1 for sensors with GSA plug-in head
CPK9 for sensors with ESA plug-in head
VBC box + CYK71
Connecting the chlorine sensors CCS140 / 141 / 240 /241
The sensors are equipped with a 3 m (9.8 ft) fixed cable. Connect the sensors to the
transmitter according to the following diagram:
Sensor with 3 m fixed cable Transmitter
Assignment Core Terminal
Outer shield S
Anode [A] red 91
Cathode [K] 90
NTC temperature sensor green 11
NTC temperature sensor brown 12
Connecting the total chlorine sensor CCS120
Connect the sensor with the measuring cable CPK9-N*A1B (with internal PML) according
to the following connection diagram:
Cable with TOP68 connection Transmitter
Pin Assignment Core Terminal
1 TC signal Coax, inside (white) 90
2 AGND Coax, outside (black) 12
3
4 +UB (15 V) green 85
5 NTC1 yellow* 11
NTC1 white* 11
6 NTC2/AGND brown 86
S Shielding S S
* The white and yellow wires are interconnected in the TOP68 connector.
Liquisys M CCM223/253 Electrical connection
Endress+Hauser 25
1
2
3
5
6
4
1
2
3
5
6
4
A0026048
 14 TOP68 connection; pin arrangement of connector and coupling (shown from contact side)
Connecting the chlorine sensor 963
The chlorine sensor 963 is supplied without a temperature sensor ex factory. Connect the
chlorine sensor to the transmitter as follows:
Without temperature measurement:
Connect the 10 kΩ equivalent resistor supplied to terminals 11 and 12. The measured
value display will then constantly show 25 °C (77 °F).
With temperature measurement:
Mount an NTC temperature sensor 10 kΩ / 25 °C (77 °F) (120 mm installation version
TSP 3692) in the chlorine sensor 963. Use the CPK1 connecting able to connect the
temperature sensor to terminals 11 and 12.
Chlorine sensor:
Connect the red cable to terminal 92 (cathode) and the blue cable to terminal 91
(anode).
Connection of pH or ORP sensors
Connect the pH or ORP sensor always symmetrically to prevent a mutual interference of
several sensors mounted in the CCA250 assembly.
Symmetrical connection requires a potential matching pin. The pin is integrated as
standard in the CCA250 flow assembly and is connected by a PML to the PA/PM terminal.
CPK1
CPK9
PM
pH / Redox
PM
pH + Pt 100 / Pt 1000
Coax Ref.
pH or Redox
BN PM
Coax BK Ref.
inner pH
GN Temp.
WH Temp.
YE Temp.
BN PM
A0002330-EN
 15 Connection of the pH or ORP sensor to the field instrument with the cables CPK1 or CPK9
Electrical connection Liquisys M CCM223/253
26 Endress+Hauser
If you are using glass electrodes with the panel-mounted device, you have to terminate the
measuring cable with a BNC connector. A solder-free BNC connector is supplied with the
device. To do this, proceed as follows:
1. Cut off end ferrules 2 and 3 of the coaxial cable.
3
4
1
2
A0005744
 16 Cable CPK1: device connection
1 Coax cable
2 Inner shield BK (ref)
3 Inner coax (pH / mV)
4 Strand BN (PA)
2. Push the cable gland 5 and the washer 6 onto the
coaxial cable.
5 6
5 6
7
8
14
13 (0.51)
16 (0.63)
A0005745
 17 Terminating the pH connecting cable for
mounting the BNC elbow plug. Dimensions in
mm (inch)
3. Remove the insulation (13 mm (0.51")) and screw the
clamping ring 7 onto the insulation.
Parts 5 to 7 are supplied with the BNC
connector for cable diameters 3.2 mm and
5 mm.
4. Fold the braided shield 8 of the shield over the
clamping ring and cut off the excess material.
5. There is a semiconductor layer 14 (conductive
membrane) between the inner insulation and the
braided shield 8. Strip this semiconductor layer as far
as the braided shield.
6. Remove the inner insulation (4 mm (0.16")), fit end
ferrule 13 on the stripped inner conductor and secure
the end ferrule with a crimping pliers.
13
4 (0.16)
A0005746
 18 Terminating the pH connecting cable for
mounting the BNC elbow plug. Dimensions in
mm (inch)
7. Push the BNC connector housing 9 over the cable. The
inner conductor must be located on the clamping
surface 10 of the connector.
5
9
10
11
12
A0005747
 19 Mounting the pH connecting cable in the BNC
elbow plug
8. Tighten the cable gland 5.
9. Insert the clamp element 11 and screw in the
connector cover 12. This creates a safe connection
between the inner conductor and the connector pin.
Liquisys M CCM223/253 Electrical connection
Endress+Hauser 27
Sensor Maximum cable length
Chlorine/chlorine dioxide sensors CCS140/141/240/ 241 Max. 30 m (98.4 ft) with cable CMK
Chlorine sensor 963 Max. 30 m (98.4 ft) with cable MK
Total chlorine sensor CCS120 Max. 15 m (49.2 ft) with cable CYK71
pH/ORP measurement Max. 50 m (164 ft) with cable CYK71
Use the junction box VBC and the appropriate extension cable to extend the measuring
cable.
2 x Pg 7
2 x Pg 11
5 x Pg 7
A
B
B
54 (2.13)
113 (4.45)
125 (4.92)
52 (2.05)
A0005740
 20 Junction box VBC with grounding point
A View in arrow direction
B 2 fixing bore holes Ø 4.5 mm (0.18")
BN
GN
1
2
3
4
5
6
7
8
A0002331
 21 Structure of cable CMK
1 Outer shield
2 Inner shield, anode
3 Semi-conductor layer
4 Inner insulation
5 Inner conductor, measuring signal
6 Temperature sensor connection
7 2nd insulation
8 Outer insulation
1
2 3
45
6
7
A0002332
 22 Structure of cable CYK71
1 Outer shield
2 Inner shield, reference signal
3 Inner insulation
4 Inner conductor, measuring signal
5 Semi-conductor layer
6 2nd insulation
7 Outer insulation
NOTICE
Incorrect measurement due to short-circuit
Make sure to remove the black semiconductor layer as far as the inner shield when
connecting cable CMK and CYK71.
Electrical connection Liquisys M CCM223/253
28 Endress+Hauser
5.6 Three-point step controller for Cl
2
/ ClO
2
/ total
chlorine
Connect the continuously variable motor valves as follows:
1. Connect the NO contact of the motor valve to relay 3.
2. Connect the NC contact of the motor valve to relay 4.
Liquisys M CCM223/253 Electrical connection
Endress+Hauser 29
5.7 Alarm contact
41
42
43
41
42
43
A
B
A0006415
 23 Recommended fail-safe switching for the alarm contact
A Normal operating status
B Alarm condition
Normal operating status Alarm condition
Device in operation and no error message
present (alarm LED off):
Relay energized
Contact 42/43 closed
Error message present (alarm LED red) or device
defective or de-energized (alarm LED off):
Relay de-energized
Contact 41/42 closed
5.8 Post-connection check
Carry out the following checks once you have made the electrical connection:
Device state and specifications Notes
Are the devices and cables free from damage on the outside? Visual inspection
Electrical connection Notes
Are the mounted cables strain relieved?
Are the connected cables provided with strain relief?
Is the cable run correct, without loops and cross-overs?
Are the power cable and signal cables connected correctly and in
accordance with the wiring diagram?
Are all the screw terminals tightened?
Are all the cable entries fitted, tightened and leak-proof?
Operation options Liquisys M CCM223/253
30 Endress+Hauser
6 Operation options
6.1 Quick operation guide
You have the following ways of operating the transmitter:
On site via the key field
Via the HART interface (optional, with corresponding order version) with:
HART handheld terminal
PC with HART modem and the Fieldcare software package
Via PROFIBUS PA/DP (optional, with corresponding order version) by PC with a
corresponding interface and the Fieldcare software package or via a programmable logic
controller (PLC).
For operation via HART or PROFIBUS PA/DP, please read the relevant sections in the
additional Operating Instructions:
PROFIBUS PA/DP, field communication for Liquisys M CXM223/253,
BA00209C/07/EN
HART, field communication for Liquisys M CXM223/253, BA00208C/07/EN
The following section only explains operation via the keys.
6.2 Display and operating elements
6.2.1 Display
LED displays
A0027220
Indicates the current operating mode, "Auto" (green LED) or
"Manual" (yellow LED)
A0027222
Indicates the activated relay in the "Manual" mode (red LED)
The status of relays 3 and 4 is indicated on the LC display.
A0027221
Indicates the working status of relay 1 and 2
LED green: measured value within the permitted limit, relay
inactive
LED red: measured value outside the permitted limit, relay active
A0027218
Alarm display, e.g. in event of continuous limit value overshoot,
temperature sensor failure or system error (see error list)
Liquisys M CCM223/253 Operation options
Endress+Hauser 31
LC display
mg/l
R242
1
2 3
4
5
6
7
8
9
12
13
14
0 4 2
10
11
Setpoint
A0001924-EN
 24 Transmitter LC display
1 Indicator for measuring mode (normal operation)
2 Indicator for calibration mode
3 Indicator for setup mode (configuration)
4 Indicator for "Hold" mode (current outputs remain at last current state)
5 Indicator for receipt of a message on devices with communication
6 Indicator of working status of relays 3/4: inactive, active
7 Function code
8 In measuring mode: measured variable - in setup mode: configured variable
9 In measuring mode: secondary measured value - in setup/calibr. mode: e.g. set value
10 Indicator for autom. Temperature compensation
11 Indicator for man. Temperature compensation
12 "Error": error display
13 Temperature offset
14 Sensor symbol (see the "Calibration" section)
Operation options Liquisys M CCM223/253
32 Endress+Hauser
6.2.2 Operating elements
The display shows the current measured value and the temperature simultaneously, which
means you have an overview of the most important process data at once. Help text in the
configuration menu helps users configure the device parameters.
1
7
6
4
5
3
2
A0024631-EN
 25 Operating elements
1 LC display for displaying the measured values and configuration data
2 Key to switch relays in manual mode and to display the active contact
3 LED for alarm function
4 Changeover switch for automatic/manual mode
5 LEDs for limit contactor relay (switch status)
6 Main operating keys for calibration and device configuration
7 Field for user-defined information
6.2.3 Key functions
A0027235
CAL key
When you press the CAL key, the device first prompts you for the
calibration access code:
Code 22 for calibration
Code 0 or any other code for reading the last calibration data
Use the CAL key to accept the calibration data or to switch from
field to field within the calibration menu.
A0027236
ENTER key
When you press the ENTER key, the device first prompts you for the
setup mode access code:
Code 22 for setup and configuration
Code 0 or any other code for reading all the configuration data.
The ENTER key has several functions:
Calls up the Setup menu from the measuring mode
Saves (confirms) data entered in the setup mode
Moves on within function groups
Liquisys M CCM223/253 Operation options
Endress+Hauser 33
A0027240
PLUS key and MINUS key
In the Setup mode, the PLUS and MINUS keys have the following
functions:
Selection of function groups.
Press the MINUS key to select the function groups in the order
given in the "System configuration" section.
Configuration of parameters and numerical values
Operation of the relays in manual mode
In the measuring mode, the following sequence of functions is
accessed by repeatedly pressing the PLUS key:
Temperature displayed in °F
Temperature is hidden
pH measured value or ORP (only for EP version)
pH sensor signal in mV (only for EP version)
Sensor current of chlorine/chlorine dioxide sensor in nA
Zero current of sensor CCS120
Current input signal in %
Current input signal in mA
Return to basic settings
In the measuring mode, the following sequence of information is
displayed by repeatedly pressing the MINUS key:
The current errors are displayed consecutively (max. 10).
Once all the errors have been displayed, the standard
measurement display appears. In the function group F, an alarm
can be defined separately for each error code.
A0027241
REL key
In the manual mode, you can use the REL key to switch between the
relay and the manual start of cleaning.
In automatic mode, you can use the REL key to read out the switch-
on points (for limit contactor) or set points (for PID controller)
assigned to the relay in question.
Press the PLUS key to jump to the settings of the next relay. Use the
REL key to get back to the display mode (automatic return after
30 s).
A0027234
AUTO key
Use the AUTO key to switch between automatic mode and manual
mode.
A0027237
Escape function
If you press the PLUS and MINUS key simultaneously, you return to
the main menu, or are taken to the end of calibration if calibrating.
If you press the PLUS and MINUS key again, you return to the
measuring mode.
Operation options Liquisys M CCM223/253
34 Endress+Hauser
A0027238
Locking the keyboard
Press the PLUS and ENTER key simultaneously for at least 3 s to
lock the keyboard against any unauthorized data entry. All the
settings can continue to be read.
The code prompt displays the code 9999.
A0027239
Unlocking the keyboard
Press the CAL and MINUS key simultaneously for at least 3 s to
unlock the keyboard.
The code prompt displays the code 0.
Liquisys M CCM223/253 Operation options
Endress+Hauser 35
6.3 Local operation
6.3.1 Automatic/manual mode
The transmitter normally operates in automatic mode. Here, the relays are triggered by
the transmitter. In the manual mode, you can trigger the relays manually using the REL
key or start the cleaning function.
How to change the operating mode:
A0027242
1. The transmitter is in automatic mode. The top LED (green)
next to the AUTO key is lit.
A0027243
2. Press the AUTOMATIC key.
A0027240
3. To enable the manual mode, enter the code 22 via the PLUS
and MINUS keys and press ENTER to confirm.
The lower LED (manual mode) is lit.
A0027241
4. Select the relay or the function.
You can use the REL key to switch between the relays. The
relay selected and the switch status (ON/OFF) is displayed on
the second line of the display.
In the manual mode, the measured value is displayed
continuously (e.g. for measured value monitoring for dosing
functions).
A0027240
5. Switch the relay. The relay is switched on with PLUS and
switched off with MINUS.
The relay remains in this switched state until it is switched
again.
A0027234
6. Press the AUTOMATIC key to return to the measuring mode,
i.e. to the automatic mode.
All the relays are triggered again by the transmitter.
The operating mode remains in effect even after a power failure. The relays assume
the quiescent state, however.
The manual mode has priority over all other automatic functions.
Hardware locking is not possible in the manual mode.
The manual settings are kept until they are actively reset.
Error code E102 is signaled during manual operation.
Operation options Liquisys M CCM223/253
36 Endress+Hauser
6.3.2 Operating concept
Operating modes
Code
Measuring mode:
standard mode of
operation, displaying
current measured values
Setup mode
access to all
configuration
settings
Calibration mode:
execution of
calibration routine
The function groups
are selected with the
PLUS or MINUS key.
A0027244-EN
 26 Description of the possible operating modes
If no key is pressed in the setup mode for approx. 15 min, the device automatically
returns to the measuring mode. Any active hold (hold during setup) is canceled.
Access codes
All device access codes are fixed and cannot be altered. When the device requests the
access code, it distinguishes between different codes.
CAL key + code 22: access to Calibration and Offset menu
ENTER key + code 22: access to the menus for the parameters which make
configuration and user-specific settings possible
PLUS + ENTER keys simultaneously (min. 3 s): lock the keyboard
CAL + MINUS keys simultaneously (min. 3 s): unlock the keyboard
CAL or ENTER key + any code: access to read mode, i.e. all the settings can be read but
not modified.
The device continues measuring in the read mode. It does not shift to the "Hold" status.
The current output and the controllers remain active.
Liquisys M CCM223/253 Operation options
Endress+Hauser 37
Menu structure
The configuration and calibration functions are arranged in function groups.
In the setup mode, select a function group with the PLUS and MINUS keys.
In the function group itself, switch from function to function with the ENTER key.
Within the function, select the desired option with the PLUS and MINUS keys or edit the
settings with these keys. Then confirm with the ENTER key and continue.
Press the PLUS and MINUS keys simultaneously (Escape function) to exit programming
(return to the main menu).
Press the PLUS and MINUS keys simultaneously again to switch to the measuring mode.
If a modified setting is not confirmed by pressing ENTER, the old setting is retained.
An overview of the menu structure is provided in the Appendix to these Operating
Instructions.
E E
-
1
2
3
E
E
E
E
A0027245
 27 Menu structure
1 Functions (selection of parameters, entry of numbers)
2 Function groups, scroll backwards and forwards with the PLUS and MINUS keys
3 Switch from function to function with the ENTER key
Hold function: "freeze" the outputs
In both the setup mode and during calibration, the current output can be "frozen" (factory
setting), i.e. it constantly retains its current status. "HOLD" appears on the display. If the
controller actuating variable (steady control 4 to 20 mA) is output via current output 2, it
is set to 0/4 mA during a hold.
Hold settings can be found in the "Service" function group.
During a hold, all contacts assume a quiescent state.
An active hold has priority over all other automatic functions.
With every hold, the I-component of the controller is set to "0".
Any alarm delay is reset to "0".
This function can also be activated externally via the hold input (see Wiring diagram;
binary input 1).
A manual hold (field S3) remains active even after a power failure.
Commissioning Liquisys M CCM223/253
38 Endress+Hauser
7 Commissioning
7.1 Function check
L
WARNING
Incorrect connection, incorrect supply voltage
Safety risks for staff and device malfunctions
Check that all connections have been established correctly in accordance with the
wiring diagram.
Ensure that the supply voltage matches the voltage indicated on the nameplate.
7.2 Switching on
Familiarize yourself with the operation of the transmitter before it is first switched on. In
particular please read the "Basic safety instructions" and "Operation options" sections. After
power-up, the device performs a self-test and then goes to the measuring mode.
Now calibrate the sensor in accordance with the instructions in the "Calibration" section.
During initial commissioning, the sensor must be calibrated so that the measuring
system can return precise measurement data.
Then perform the first configuration in accordance with the instructions in the "Quick
setup" section. The values set by the user are kept even in the event of a power failure.
The following function groups are available in the transmitter (the groups that are only
available in the Plus Package are marked accordingly in the functional description):
Setup mode
SETUP 1 (A)
SETUP 2 (B)
CURRENT INPUT (Z)
CURRENT OUTPUT (O)
ALARM (F)
CHECK (P)
RELAY (R)
SERVICE (S)
E+H SERVICE (E)
INTERFACE (I)
Calibration and offset mode
CALIBRATION (C)
A detailed explanation of the function groups available in the transmitter can be
found in the "Device configuration" section.
s
F3
Err.delay
Function display:
The displayed code indicates
the function position in the
function group.
Additional information
2
A0025560-EN
 28 Information for the user on the display
Liquisys M CCM223/253 Commissioning
Endress+Hauser 39
C C1 C111
C121
C131
C132 C133
A0027502
 29 Function code
To make it easier for you to select and find function
groups and functions, a code for the corresponding
field is displayed for each function →  28
The structure of this code is illustrated in →  29.
The function groups are indicated as letters in the first
column (see the names of the function groups). The
functions of the individual groups are displayed
incrementally by row and by column.
Factory settings
The first time the device is switched on, the factory setting is set for all the functions. The
table below provides an overview of the most important settings.
All other factory settings can be found in the description of the individual function groups
in the "System configuration" section (the factory setting is highlighted in bold).
Function Factory setting
Type of measurement Concentration of free chlorine/total chlorine in
mg/l
Temperature measurement in °C
pH value (EP version)
Sensor setting CCS140 for free chlorine
Alarm contact Steady contact
Alarm delay Setting in minutes
Error current for alarm 22 mA
Check functions* Off. Can be switched on if required
Limit value 1 and 2 for chlorine/chlorine dioxide 0.5 mg/l
Limit value 1 and 2 for pH* pH 7.2
Limit value 1 and 2 for ORP* 750 mV
Limit value 1 and 2 for temperature 50 °C
Current outputs 1 and 2 4 to 20 mA
Current output 1: measured value for 4 mA signal current 0.00 mg/l
Current output 1: measured value for 20 mA signal current 2.00 mg/l
Current output 2: temperature value for 4 mA signal current* 0 °C
Current output 2: temperature value for 20 mA signal current* 50 °C
* with appropriate version
Commissioning Liquisys M CCM223/253
40 Endress+Hauser
7.3 Quick Setup
After power-up, you must make some settings to configure the most important functions
of the transmitter which are required for correct measurement. The following section gives
an example of this.
User entry Range of
adjustment
(factory settings in
bold)
Display
1. Press the ENTER key
2. Enter the code 22 to open access to the menus.
Press the ENTER key.
3. Press the MINUS key until you get to the "Service"
function group.
S
SERVICE
A0008408-EN
4. Press ENTER to be able to make your settings.
5. Select your language in S1, e.g. "ENG" for English.
Press ENTER to confirm your entry.
ENG = English
GER = German
FRA = French
ITA = Italian
NEL = Dutch
ESP = Spanish
S1
Language
ENG
A0008409-EN
6. Press the PLUS and MINUS key simultaneously to
exit the "Service" function group.
7. Press the MINUS key until you get to the "Setup 1"
function group.
A
SETUP 1
A0007824-EN
8. Press ENTER to be able to make your settings for
"Setup 1".
9. In A1, select the desired sensor type.
Press ENTER to confirm your entry.
120 = CCS120
140 = CCS140
141 = CCS141
240 = CCS240
241 = CCS241
963
A1
Sensor
140
A0001954-EN
10. In A2, select the desired engineering unit.
Press ENTER to confirm your entry.
mg/l
ppm
ppb
A2
Unit
mg/l
A0024894-EN
11. If you have connected the INS proximity switch, you
can switch on flow monitoring of the sample
stream through the CCA250 assembly in A3.
Press ENTER to confirm your entry.
Off
INS
A3
Cont.stop
Off
A0001956-EN
12. If flow briefly falls below the threshold value, you
can suppress controller switch-off by entering a
delay time in A4.
Press ENTER to confirm your entry.
0 s
0 to 2000 s
A4
s
Off Delay
0
A0001957-EN
Liquisys M CCM223/253 Commissioning
Endress+Hauser 41
User entry Range of
adjustment
(factory settings in
bold)
Display
13. In A5, enter the delay time for controller switch-
on.
In the case of chlorine/chlorine dioxide control, a
delay until the reception of a representative
measured value is recommended after a long
period without flow.
Press ENTER to confirm your entry.
0 s
0 to 2000 s
A5
s
On Delay
0
A0001958-EN
14. In A6, select the binary input.
Press ENTER to confirm your entry.
Hold = external
hold
Clean = cleaning
trigger
A6
Digital 1
Hold
A0001959-EN
15. In A7, enter the measured value damping.
Measured value damping causes the measured
value to be averaged over the specified number of
individual measured values (if A7 = 1, no damping
takes place).
Press ENTER to confirm your entry.
The display returns to the initial display of the
"Setup 1" function group.
1
1 to 60
A7
Damping
1
A0001960-EN
16. Press PLUS and MINUS simultaneously to switch to
the measurement mode.
Commissioning Liquisys M CCM223/253
42 Endress+Hauser
7.4 Device configuration
7.4.1 Setup 1 (chlorine/chlorine dioxide)
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
A
SETUP 1 function
group
A
SETUP 1
A0007824-EN
Configuration of basic
functions
A1 Select the connected
sensor type
120 = CCS120
140 = CCS140
240 = CCS240
241 = CCS241
963
A1
Sensor
140
A0001954-EN
If the device is reset in
field S9, the configured
sensor type is not
modified.
A2 Select the display
unit
mg/l
ppm
ppb
A2
Unit
mg/l
A0001955-EN
A3 Select flow
monitoring of the
sample flow through
the CCA250
assembly (with
controller switch-
off)
Off
INS
A3
Cont.stop
Off
A0001956-EN
May only be switched on
when the INS proximity
switch is connected.
A4 Enter the delay for
controller switch-off
by the sample flow
0 s
0 to 2000 s
A4
s
Off Delay
0
A0001957-EN
Brief flow shortfalls can
be suppressed by this
delay and do not result in
controller switch-off.
A5 Enter the delay for
controller switch-on
by the sample flow
0 s
0 to 2000 s
A5
s
On Delay
0
A0001958-EN
In the case of chlorine/
chlorine dioxide control, a
delay until the reception
of a representative
measured value is
recommended after a
long period without flow.
A6 Select binary input 1 Hold = external
hold
Clean = cleaning
trigger
A6
Digital 1
Hold
A0001959-EN
A7 Enter the value for
measured value
damping
1
1 to 60
A7
Damping
1
A0001960-EN
Liquisys M CCM223/253 Commissioning
Endress+Hauser 43
Flow monitoring in the sample stream
If the flow falls below 30 l/h or if sample flow through the CCA250 assembly fails
completely, this causes an alarm to be signaled when an INS proximity switch is connected.
This alarm becomes active when the switch-off delay time elapses (A4 field). The alarm is
canceled immediately as soon as the necessary rate of flow is restored. The device
automatically stops the dosing of chemicals and the Chemoclean cleaning function for the
duration of the alarm. All the relays assigned to the PID controller or to a cleaning function
go to the quiescent state. The NO contact closes in the case of the three-point step
controller. Dosing and cleaning actions are only resumed once the switch-on delay time
has elapsed (A5 field).
0
1
1
1
1
0
0
0
A
B
C
D
E
F
G
A4
A4
A5
A5
A0002018
 30 Alarm signaling and dosing switch-off by the sample stream
A Flow in sample stream
B Relay contacts of PID controller
C NO contact on three-point step controller
D Alarm relay
E Flow < 30 l/h or flow failure
F Flow alarm
G Flow restored
0 Off
1 On
A4 Field A4 (controller switch-off delay)
A5 Field A5 (controller switch-on delay)
Commissioning Liquisys M CCM223/253
44 Endress+Hauser
7.4.2 Setup 2 (temperature or pH/ORP)
Use this function group to change the settings for temperature measurement and pH/ORP
measurement.
You already made all the settings for this function group during initial commissioning.
However, you can change the values chosen at any time.
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
B
SETUP 2
function group
B
SETUP 2
A0007830-EN
Initial display screen in the
SETUP 2 function group
B1 Select operating
mode
Off
pH
ORPmV
B1
Oper.Mode
Off
A0001963-EN
Field only available for EP
version.
ORPmV = ORP (oxidation-
reduction potential) in mV.
When the operating mode is
changed, all user settings are
automatically reset to the basic
settings.
If the device is reset in field
S9, the configured operating
mode is not modified.
B2 Select pH
compensation
Off
Manu
Auto
B2
pH comp.
Off
A0001964-EN
Field only available for ES and
EP versions. (operation with
CCS140/141)
B3 Enter the value
for manual pH
compensation
Last
compensation
value
pH 4.00 to 9.00
B3
pH
7.20
Manu.Comp
A0001965-EN
The field is only displayed if »
manual« (Manu) was selected
in the B2 field.
The measured pH value is
displayed as the secondary
parameter.
B4 Enter the
process
temperature
Current
measured value
0 to 50 °C
B4
¡C
RealTemp.
0.0
A0001966-EN
You can edit the displayed
value.
The value can be changed by a
maximum of ±5 °C.
As the measurements are very
accurate, the value generally
does not need to be adjusted.
B5 Enter the
temperature
differential
(offset)
Current offset
-5.0 to 5.0 °C
¡
C
B5
Temp.Offs
0.0
A0007835-EN
The offset is the difference
between the actual value
entered and the measured
temperature.
Types of chlorine
A distinction is made between free chlorine and combined chlorine.
Free chlorine
Liquisys M CCM223/253 Commissioning
Endress+Hauser 45
Free chlorine is understood as the sum of elementary chlorine (Cl
2
), hypochlorous acid
(HOCl) and hypochlorite ions (OCl
). These forms of chlorine are able to kill bacteria,
inactivate viruses and oxidize organic substances within a short period of time.
Combined chlorine
Combined chlorine refers to the forms of chlorine in water and consists of chemical
compounds made up of chlorine and ammonia (NH
3
) or ammonium (NH
4
+
) entstehen.
Combined chlorine still has a disinfectant property, but far less than that of free chlorine.
Total chlorine
Total chlorine is the sum of free chlorine and combined chlorine.
Measuring free chlorine with the CCS140 and CCS141 sensors
Molecular chlorine (Cl
2
) is present at pH values < 4. Consequently, hypochlorous acid
(HOCl) and hypochlorite (OCl– remain as components of free chlorine within the range of
pH 4 to 11.
As hypochlorous acid splits up (dissociates) with an increasing pH value to form
hypochlorite ions (OCl
) and hydrogen ions (H
+
), the amounts of the individual
components of free effective chlorine change with the pH value. For example, if the
amount of hypochlorous acid is 97% at pH 6, it drops to approx. 3% at pH 9.
%
100
80
60
40
20
0
4
5 6 7 8 9 10 11
100
%
80
60
40
20
0
A
B
C
pH
OCl
-
HOCl
A0002017
 31 Basic representation of pH compensation
A Measured value with pH compensation
B Measured value without pH compensation
C pH compensation
The CCS140 or CCS141 chlorine sensors selectively measure the amount of hypochlorous
acid in amperometric measurement.. This works as a powerful disinfectant in a watery
solution. In contrast to this, hypochlorite is an extremely weak disinfectant. Therefore,
when used as a disinfectant at higher pH values, the effectiveness of chlorine is limited. As
hypochlorite ions cannot permeate the sensor membrane, the sensors do not record this
value.
Measuring total chlorine with the CCS120 sensor
If, in addition to free available chlorine, ammonium is also present in the medium -
preferably water - chloramines (Cl
n
NH
m
) form quickly. This compound is formed in various
Commissioning Liquisys M CCM223/253
46 Endress+Hauser
degrees of dimerization. It is known as "combined chlorine". Combined chlorine has a lower
disinfecting effect but it forms larger depots compared to free chlorine. This means:
Significantly slower elimination of existing germs.
Disinfectant effect over considerably longer periods.
Disinfectant effect over considerably longer transport distances.
The CCS120 amperometric sensor measures the total chlorine content, i.e. free chlorine as
well as chloramine components.
This type of measurement is only slightly pH dependent.
pH compensation of the chlorine sensor signal during free chlorine measurement
(only for ES and EP versions, for CCS140/141 sensors)
To calibrate and verify the chlorine measuring system, a colorimetric reference
measurement must be carried out using the DPD method. Free chlorine reacts with
diethyl-p-phenylendiamine to form a red dye. The intensity of the red color increases
proportionally to the chlorine content. With the DPD method, the water under
measurement is constantly buffered to a pH value of approx. 6.3. Therefore, the pH value
of the water under measurement is not included in the DPD measurement here. Due to the
buffer function in the DPD method, all components of free effective chlorine are recorded
and thus the total free chlorine is measured.
If you select pH compensation in fields B2 or B3, the sum of hypochlorous acid and
hypochlorite corresponding to the DPD measurement is calculated from the hypochlorous
acid measured by the sensor and the pH value in the region of pH 4 to 9. For this
calculation, the curve is stored in the transmitter.
When free chlorine is measured with pH compensation switched on, always perform
calibration in pH-compensated mode.
When you use pH compensation, the measured chlorine value that is displayed and applied
to the device output corresponds to the DPD measured value even if the pH values
fluctuate. If you do not use pH compensation, the measured chlorine value corresponds to
the DPD measurement only if the pH value remains unchanged compared with the
calibration. Without pH compensation, the chlorine measuring system must be
recalibrated when the pH value changes.
pH compensation can be performed both automatically using the connected pH electrode
(EP version) and manually (ES version) by entering the pH value in the B3 field.
Chlorine dioxide and total chlorine measurement is largely or entirely independent of the
pH value and therefore no pH compensation is required.
Accuracy of pH compensation when measuring free chlorine
The accuracy of the pH-compensated measured chlorine value is derived from the sum of
several individual deviations (chlorine, pH, temperature, DPD measurement etc.).
High levels of hypochlorous acid (HOCl) during chlorine calibration have a positive effect
on accuracy, whereas low levels of hypochlorous acid have a negative effect.
The inaccuracy of the pH-compensated measured chlorine value increases the greater the
pH difference between measuring mode and chlorine calibration or the more inaccurate
the underlying individual measured values are.
Calibration of free chlorine taking the pH value into consideration
The reference measurement (DPD method, photometer) determines the total free chlorine
by buffering to pH 6.2. In contrast to this, amperometric measurement determines only
the HOCl component.
During operation, pH compensation is effective up to a pH value of 9. However, there is
hardly any HOCl left at this pH value, and the measured current is very low. At this point,
pH compensation has the effect of increasing the measured HOCl value to the actual value
of the free chlorine.
Liquisys M CCM223/253 Commissioning
Endress+Hauser 47
Calibration of the complete measuring system makes sense only up to a pH value of the
medium of 8 or 8.2.
Sensor pH value HOCl content Uncompensated value Compensated value
CCS141 8.2 15 % 12 nA 80 nA
CCS140 8 20 % 4 nA 20 nA
Above these pH values, the total error of the measuring system is unacceptably high.
7.4.3 Current input
For the "Current input" function group, you require a relay card with a current input which
is not available in the basic device version. With this function group, you can monitor
process parameters and use them for feedforward control. For this purpose, you must
connect the current output of an external measured variable (e.g. flowmeter) to the 4 to
20mA input of the transmitter. The following assignment applies:
Flow in main stream Current signal in mA Current input signal in %
Flowmeter start of measuring range 4 0
Flowmeter end of measuring range 20 100
Flow monitoring in the main stream
This arrangement is particularly practical if the sample flow through the CCA250 assembly
is completely independent of the flow in the main stream.
This permits signaling of an alarm condition in the main stream (flow too low or has
completely stopped) and triggers dosing switch-off even if the medium flow is maintained
due to the method of installation.
This monitoring method corresponds to monitoring the flow rate in the sample stream
(see SETUP 1).
0
1
1
1
1
0
0
0
A
B
C
D
E
F
G
Z2
Z2
Z3
Z3
A0002019
 32 Alarm signaling and dosing switch-off by the main stream
A Flow in main stream F Flow alarm
B Relay contacts of PID controller G Flow restoration
Commissioning Liquisys M CCM223/253
48 Endress+Hauser
C NO contact on three-point step controller Z2 Delay for controller switch-off, see field Z2
D Alarm relay Z3 Delay for controller switch-on, see field Z3
E Flow below switch-off limit Z 4 or flow failure 0 Off
1 On
Feedforward control to PID controller
You can optimize control on control systems with very short response times by measuring
the medium flow rate in addition to the oxygen content. Then apply this flow rate value (4
to 20 mA) as feedforward control to the PID controller.
F
4 ... 20 mA
Cl
2
pH
1
2
3
4
5
6
ENDRESS+HAUSER
LIQUISYS S
A0025120
 33 Sample arrangement for feedforward control of the flow in the main stream to the PID controller
1 Medium tapping point 5 Flow assembly CCA250
2 Static mixer 6 Liquisys CCM253
3 Injection points
4 Flowmeter
Feedforward control is a multiplying function as illustrated in the figure below (example
with factory setting):
Liquisys M CCM223/253 Commissioning
Endress+Hauser 49
1
0 20 40 60 80 100Z7
1.5
0.5
Y
X
A0008942
 34 Multiplying feedforward control
Y Gain K
infl
X Current input signal in [%]
Commissioning Liquisys M CCM223/253
50 Endress+Hauser
Functions marked in italics are not supported by the basic device version.
Coding Field Range of
adjustment
(factory
settings in
bold)
Display Info
Z
CURRENT INPUT
function group
Z
CUR.INPUT
A0024903-EN
Current input settings
Z1 Select flow
monitoring of main
stream (with
controller switch-
off)
Off
On
Z1
Cont.stop
Off
A0024904-EN
Flow monitoring may only be
switched on if the flowmeter is
connected in the main stream. If
Z1 = off, fields Z2 to Z5 are not
available.
Z2 Enter the delay for
controller switch-
off through current
input
0 s
0 to 2000 s
Z2
s
Off Delay
0
A0024905-EN
Brief flow shortfalls can be
suppressed by this delay and do
not result in controller switch-
off.
Z3 Enter the delay for
controller switch-
on through current
input
0 s
0 to 2000 s
Z3
s
On Delay
0
A0024934-EN
In the case of a controller, a
delay until the reception of a
representative measured value
is recommended after a long
period without flow.
Z4 Enter the switch-off
limit value for the
current input
50 %
0 to 100 %
Z4
%
A.Thresh
50
A0024935-EN
0 to 100% corresponds to 4 to
20 mA at the current input.
Observe measured value
assignment to the current
output of the flowmeter.
Z5 Enter the switch-off
direction for the
current input
Low
High
Z5
Stop Dir
Low
A0024939-EN
The controller is switched off if
the value entered in Z4 is
undershot or overshot.
Z6 Select feedforward
control to PID
controller
Off
Lin = linear
Basic
Z6
PID influ
Off
A0024940-EN
If Z6 = off, the field Z7 is not
available.
Z6 = basic: disturbance variable
only affects the basic load
(alternatively dosing in
proportion to quantity, if usual
PID controller not possible, e.g.
defective sensor).
Z7 Enter value for
feedforward control
at which gain = 1
applies
50 %
0 to 100 %
Z7
%
Kinflu=1
50
A0024941-EN
When the value is set, the
controller actuating variable is
the same size when feedforward
control is switched on as when
feedforward control is switched
off.
Liquisys M CCM223/253 Commissioning
Endress+Hauser 51
7.4.4 Current outputs
Use the "Current output" function group to configure the individual outputs. You can enter
either a linear characteristic (O3 (1)) or a user-defined current output characteristic in
conjunction with the Plus Package (O3 (3)). Exception: if you have chosen a "continuous
controller" for current output 2, you cannot enter a user-defined current output
characteristic for this current output.
In addition, you can also simulate a current output value (O3 (2)) to check the current
outputs.
1
0 4 8 12 16 20
2
Cl
[mg/l]
[mA]
Δ
S
i
g
n
a
l
Δ[mA]
A0002021
 35 User-defined current output characteristic (example)
The current output characteristic must increase or decrease very monotonically.
The distance per mA between two table value pairs must be greater than:
Sensor/measurement parameter Minimum distance per mA
CCS120 0.005 mg/l
CCS140/240 0.01 mg/l
CCS141/241 and 963 0.003 mg/l
pH pH 0.03
ORP 5 mV
Temperature 0.25 °C
The values for the sample characteristic →  35 are entered in the following table. The
distance per mA is calculated from Δ signal / Δ mA.
Current output 1 Current output 2
Value pair Cl[mg/l] Current
[mA]
Distance
per mA
.....[] Current
[mA]
Distance
per mA
1 0 4
2 0.5 14 0.05
3 2 20 0.25
Commissioning Liquisys M CCM223/253
52 Endress+Hauser
First enter the desired current output configuration into the following blank table with a
pencil. Calculate the resulting signal distance per mA to observe the necessary minimum
slope. Then enter the values in the device.
Current output 1 Current output 2
Value pair .....[] Current
[mA]
Distance
per mA
.....[] Current
[mA]
Distance
per mA
1
2
3
4
5
6
7
8
9
10
Functions marked in italics are not supported by the basic device version.
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
O
CURRENT
OUTPUT
function group
O
OUTPUT
A0025026-EN
Configuration of the current
output (does not apply for
PROFIBUS).
O1 Select current
output
Out 1
Out 2
O1
Sel.Out
Out1
A0025027-EN
A characteristic can be selected
for every output.
O2 Select measured
variable for 2nd
current output
°C
Contr
O2
Parameter
¡C
A0025028-EN
pH or ORPmV only with EP
version and depending on
option selected in B1. R247 or
R257 =curr (current output 2)
can only be selected if
O2=Contr (controller output) is
selected.
O3 (1) Enter the
characteristic
type
Lin = linear (1)
Sim = simulation
(2)
Tab = table (3)
O3
Sel.Type
lin
A0025029-EN
The characteristic can have a
positive or negative slope for
the measured value output.
In the case of actuating
variable output (O2 = Contr),
an increasing current
corresponds to an increasing
actuating variable.
Liquisys M CCM223/253 Commissioning
Endress+Hauser 53
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
O311 Select current
range
4 to 20mA
0 to 20 mA
O311
Sel.Range
4-20
A0025030-EN
O312 0/4 mA value:
Enter the
associated
measured value
0 ppb
0 to 20000 ppb
0.00 ppm
0 to 20 ppm
0.00 mg/l
0 to 20 (5) mg/l
pH 4.00
pH 4 to 9
0 mV
0 to 1500 mV
0 °C
0 to 50 °C
O312
mg/l
0/4 mA
0.00
A0001944-EN
Here you can enter the
measured value at which the
min. current value (0/4 mA) is
applied at the transmitter
output (not for controller).
For the minimum distance
between the 0/4 mA and 20
mA value, see field O313
This field is not displayed if O2
= Contr.
O313 20 mA value:
Enter the
associated
measured value
2000 ppb
0 to 20000 ppb
2.00 ppm
0 to 20 ppm
2.00 (0.50) mg/l
0 to 20 (5) mg/l
pH 9.00
pH 4 to 9
1000 mV
0 to 1500 mV
50 °C
0 to 50 °C
O313
mg/l
20 mA
2.00
A0001946-EN
Here you can enter the
measured value at which the
max. current value (20 mA) is
applied at the transmitter
output.
The minimum distance
between the 0/4 mA and 20
mA value must be as follows:
140/240: 0.2 mg/l
141/241/963: 0.05 mg/l
120: 0.1 mg/l
pH: pH 0.5
ORP: 100 mV
Temperature: 5 °C
This field is not displayed if O2
= Contr.
O3 (2) Simulate
current output
Lin = linear (1)
Sim = simulation
(2)
Tab = table (3)
O3
Sel.Type
sim
A0025039-EN
Simulation is not ended until
O3(1) or O3(3) is selected.
For further characteristics, see
O3 (1), O3 (3).
O321 Enter
simulation
value
Current value
0.00 to 22.00 mA
O321
mA
Simulat.
10.20
A0025040-EN
Entering a current value
results in this value being
directly output at the current
output.
O3 (3) Enter current
output table
Lin = linear (1)
Sim = simulation
(2)
Tab = table (3)
O3
Sel.Type
table
A0025041-EN
Only for ES and EP versions.
Values can also be
subsequently added or
modified. The values entered
are automatically sorted by
increasing current value.
For further characteristics, see
O3 (1), O3 (2).
Commissioning Liquisys M CCM223/253
54 Endress+Hauser
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
O331 Select table
option
Read
Edit
O331
Sel.Table
read
A0025042-EN
O332 Enter number of
table value pairs
1
1 to 10
O332
No.Elem.
1
A0025043-EN
Enter the number of pairs of x
and y values (measured value
and current value) here.
O333 Select table
value pair
1
1 to no. elem.
Assign
O333
Sel.Elem.
1
A0025044-EN
The system runs through the
O333 to O335 function chain
as often as indicated in O332.
"Assign" appears as the last
step. The display goes to O336
after confirmation.
O334 Enter x value 0 ppb
0 to 20000 ppb
0.00 ppm
0 to 20 ppm
0.00 mg/l
0 to 20 (5) mg/l
pH 4.00
pH 4 to 9
0 mV
0 to 1500 mV
0 °C
0 to 50 °C
O334
mg/l
Meas.val.
0.00
A0025046-EN
x value = measured value
specified by user.
O335 Enter y value 0.00 mA
0.00 to 20.00 mA
O335
mA
mA value
0.00
A0025048-EN
y value = user-defined current
value pertaining to O334.
Return to O333 until all values
are entered.
O336 Message as to
whether table
status is OK
Yes
No
O336
Status ok
yes
A0025049-EN
Back to O3.
If status = no, correct the table
(all settings made up until now
remain intact) or go back to
the measuring mode (table is
deleted).
Liquisys M CCM223/253 Commissioning
Endress+Hauser 55
7.4.5 Alarm
You can use the "Alarm" function group to define various alarms and configure output
contacts.
Each individual error can be defined to be effective or not (at the contact or as an error
current).
Functions marked in italics are not supported by the basic device version.
Coding Field Range of
adjustment
(factory
settings in
bold)
Display Info
F
ALARM
function group
F
ALARM
A0025141-EN
Alarm function settings.
F1 Select contact
type
Latch =
latching
contact
Momen =
momentary
contact
F1
Cont.Type
Latch
A0025142-EN
The option selected only applies
for the fault-signaling contact, not
for the error current.
F2 Select the time
unit for the
alarm delay
min
s
F2
Time Unit
s
A0025143-EN
F3 Enter alarm
delay
0 min (s)
0 to 2000 s
(min)
F3
s
Err.Delay
0
A0025144-EN
Depending on the option selected
in F2, the alarm delay can be
entered in s or min.
F4 Select error
current
22 mA
2.4 mA
F4
Err.Curr
22mA
A0025145-EN
If "0-20 mA" was selected in
O311, "2.4 mA" may not be
used.
F5 Select the error
number
1
1 to 255
F5
Sel.error
1
A0025146-EN
Here you can select all the errors
which should trigger an alarm. The
errors are selected by the error
numbers. Please refer to the table
in the "System error messages"
section for the meaning of the
individual error numbers. The
factory settings remain in effect
for all errors that are not edited.
F6 Set alarm
contact to be
effective for the
selected error
Yes
No
F6
Rel.Assg
yes
A0025147-EN
If “no” is selected, all the other
alarm settings are deactivated (e.g.
alarm delay). The settings
themselves are maintained. This
setting only applies to the error
currently selected in F5.
Commissioning Liquisys M CCM223/253
56 Endress+Hauser
Coding Field Range of
adjustment
(factory
settings in
bold)
Display Info
F7 Set error
current to be
effective for the
selected error
No
Yes
F7
Curr.Assg
no
A0025148-EN
The option selected in F4 is
effective or not effective in the
event of an error.
This setting only applies to the
error currently selected in F5.
F8 Automatic
cleaning
function start
No
Yes
F8
CleanTrig
no
A0025149-EN
This field is not available for
certain errors, see the
"Troubleshooting and fault
elimination" section.
F9 Select return to
menu or next
error
Next = next
error number
←R
F9
Select
next
A0025150-EN
If ←R is selected, you return to F. If
Next is selected, you go to F5.
7.4.6 Check
The CHECK function group is only available for devices with the Plus Package (ES and EP
versions).
In the CHECK function group, you can select different monitoring functions for the
measurement.
By default all monitoring functions are switched off. The Sensor Check System is adapted
to the current application conditions by adding and setting the suitable functions.
Alarm threshold monitoring
When you perform chlorine or chlorine dioxide measurements without chemical dosage
control, sensor errors lead to a measured value error, but have no impact on the process
medium (examples: monitoring measurements in water works). Sensor errors generally
cause implausibly high or low readings. This is detected and signaled by user-definable
alarm thresholds.
Controller monitoring
When you perform chlorine or chlorine dioxide measurements with simultaneous chemical
dosage control, sensor errors not only result in incorrect measured values but also directly
impact the state of the process medium.
Particularly in the case of regulated water disinfection, due to the closed control loop there
is the risk that chemical dosing will not switch on if the measured value is constantly too
high. This poses a considerable danger to process stability, and could even pose a serious
health hazard for humans. On the other hand, if the measured value is constantly too low
this results in higher operating costs and a risk of corrosion due to the continuous dosing
of chemicals.
These cases are detected and signaled using user-definable monitoring times for
maximum permitted limit value overshoot and undershoot.
Sensor activity monitoring
The effect of the process medium on the sensor can also result in incorrect measured
values. For example, severe deposit buildup on the sensor membrane can cause the
Liquisys M CCM223/253 Commissioning
Endress+Hauser 57
measuring signal to be very sluggish or not even change at all (constant signal). This
passive behavior is detected and signaled by constantly monitoring the signal activity.
Overview of SCS monitoring functions
Mode of operation Possible
setting
Alarm event Use
Alarm threshold
monitoring
(P111 to P114)
(P121 to P124)
User-definable lower
alarm threshold (AS)
User-definable upper
alarm threshold (AS)
Off - Applications with
or without
chemical dosage
control
Only lower
alarm
threshold
Lower alarm threshold
reached or undershot
Only upper
alarm
threshold
Upper alarm threshold
reached or exceeded
Lower and
upper alarm
threshold
Lower alarm threshold
reached or undershot or
upper alarm threshold
reached or exceeded
Controller monitoring
(CC: controller check,
P115 to P118
P125 to P128)
Switch-on duration
monitoring
Switch-off duration
monitoring
Off - Applications with
chemical dosage
control
On Set maximum duration
for permanent switch-on
or switch-off exceeded
Sensor activity
monitoring
(AC: alternation
check,
P115 to P118
P125 to P128)
Signal change
monitoring
Off -
On Change within 1 hour
less than
±0.01 mg/l
(CCS140/240, sensor
963)
±0.005 mg/l
(CCS141/241)
pH ±0.01
±1 mV
Applications with
or without
chemical dosage
control
Commissioning Liquisys M CCM223/253
58 Endress+Hauser
You can use the "Check" function group to monitor the measured value for permissible
upper and lower limits and trigger an alarm.
Functions marked in italics are not supported by the basic device version.
Coding Field Range of
adjustment
(factory settings in
bold)
Display Info
P
CHECK
function
group
P
CHECK
A0009045-EN
Settings for sensor and process
monitoring
P1(1) Cl2
ClO2
P1
Parameter
A0001988-EN
Cl
2
if A1 = "120", "140", "141",
"963"
ClO
2
if A1 = "240", "241"
P111 Select alarm
threshold
monitoring
Off
Low
High
LoHi = low and high
Lo!
Hi!
LoHi!
P111
A.Thresh
Off
A0001989-EN
Alarm possible with or without
controller switch-off.
xxxx = without controller
switch-off
xxxx! = with controller switch-
off
P112 Enter alarm
delay
0 min (s)
0 to 2000 min (s)
P112
min
Err.Delay
0
A0001990-EN
Depending on the option
selected in F2, the alarm delay
can be entered in s or min.
This delay must first elapse
before undershooting/
overshooting in accordance
with fields P113/P114 results
in an alarm.
P113 Enter lower
alarm
threshold
0 ppb
0 to 20000 ppb
0.00 ppm
0 to 20 ppm
0.00 mg/l
0 to 20 (5) mg/l
P113
mg/l
LowAlarm
0.00
A0001991-EN
Not applicable when P111 = off
P114 Enter upper
alarm
threshold
20000 ppb
0 to 20000 ppb
20.00 ppm
0 to 20 ppm
20.00 (5.00) mg/l
0 to 20 (5) mg/l
P114
mg/l
HighAlarm
20.00
A0001992-EN
Not applicable when P111 = off
P115 Select process
monitoring
Off
AC
CC
AC+CC
AC!
CC!
AC+CC!
P115
mg/l
ProcMonit
Off
A0001993-EN
AC = sensor activity monitoring
CC = controller monitoring
Alarm possible without or with
simultaneous controller switch-
off.
xxxx = without controller
switch-off
xxxx! = with controller switch-
off
Liquisys M CCM223/253 Commissioning
Endress+Hauser 59
Coding Field Range of
adjustment
(factory settings in
bold)
Display Info
P116 Enter
maximum
permissible
duration for
alarm
threshold
undershoot
60 min
0 to 2000 min
P116
min
Tmax Low
60
A0002006-EN
Only if P115 = CC or AC+CC
P117 Enter
maximum
permissible
duration for
alarm
threshold
overshoot
120 min
0 to 2000 min
P117
min
Tmax High
120
A0002007-EN
Only if P115 = CC or AC+CC
P118 Enter limit
value
500 ppb
0 to 20000 ppb
0.5 ppm
0 to 20 ppm
0.5 (0.1) mg/l
0 to 20 (5) mg/l
P118
mg/l
Setpoint
0.5
A0002008-EN
Limit value for monitoring
according to fields P116 and
P117.
When performing
external control from a
process control system
with an external set point,
make sure that the setting
matches that in field
P118.
P1(2) pH
ORPmV
P1
Parameter
pH
A0001997-EN
Only for EP version
pH or ORPmV is displayed
depending on the mode of
operation selected in field B1.
P121 Select alarm
threshold
monitoring
Off
Low
High
LoHi = low and high
Lo!
Hi!
LoHi!
P121
A.Thresh
Off
A0001998-EN
Alarm possible with or without
controller switch-off.
xxxx = without controller
switch-off
xxxx! = with controller switch-
off
P122 Enter alarm
delay
0 min (s)
0 to 2000 min (s)
P122
min
Err.Delay
0
A0001999-EN
Depending on the option
selected in F2, the alarm delay
can be entered in s or min.
This delay must first elapse
before undershooting/
overshooting in accordance
with fields P123/P124 results
in an alarm.
P123 Enter lower
alarm
threshold
pH 4.00
pH 4 to 8.9
0 mV
0 to 1490 mV
P123
pH
LowAlarm
4.00
A0002000-EN
Not applicable when P121 = off
P124 Enter upper
alarm
threshold
pH 9.00
pH 4.1 to 9
1500 mV
10 to 1500 mV
P124
pH
HighAlarm
9.00
A0002001-EN
Not applicable when P121 = off
Commissioning Liquisys M CCM223/253
60 Endress+Hauser
Coding Field Range of
adjustment
(factory settings in
bold)
Display Info
P125 Select process
monitoring
Off
AC
CC
AC+CC
AC!
CC!
AC+CC!
P125
ProcMonit
Off
A0002002-EN
AC = sensor activity monitoring
CC = controller monitoring
Alarm possible without or with
simultaneous controller switch-
off.
xxxx = without controller
switch-off
xxxx! = with controller switch-
off
Options CC, AC+CC, CC! and AC
+CC! can only be selected if pH
is selected in field P1(2).
P126 Enter
maximum
permissible
duration for
alarm
threshold
undershoot
60 min
0 to 2000 min
P126
min
Tmax Low
60
A0002003-EN
Only if P125 = CC or AC+CC
P127 Enter
maximum
permissible
duration for
alarm
threshold
overshoot
120 min
0 to 2000 min
P127
min
Tmax High
120
A0002004-EN
Only if P125 = CC or AC+CC
P128 Enter limit
value
pH 7.20
pH 4 to 9
P128
pH
Setpoint
7.20
A0002005-EN
Limit value for monitoring
according to fields P126 and
P127.
When performing
external control from a
process control system
with an external set point,
make sure that the setting
matches that in field
P128.
7.4.7 Relay configuration
For the "RELAY" function group, you require a relay card which is not available in the basic
device version.
The following relay contacts can be selected and configured as desired (max. four contacts,
depending on options installed):
Limit contactor for chlorine/chlorine dioxide measured value: R2 (1)
Limit contactor for pH/ORP measured value: R2 (2)
Limit contactor for temperature: R2 (3)
PID controller for chlorine/chlorine dioxide: R2 (4)
PID controller for pH: R2 (5)
Timer for cleaning function: R2 (6)
Chemoclean function: R2 (7)
Three-point step controller for chlorine/chlorine dioxide: R2 (8)
Only one function can be assigned to each relay. If a relay function is already switched on
(R211 to R281), it is switched off automatically when you select another function and
press ENTER to confirm (R2(1) to R2(8)).
Pressing the REL key allows you to display the corresponding setpoint of every relay
function.
Liquisys M CCM223/253 Commissioning
Endress+Hauser 61
Limit contactors for chlorine/chlorine dioxide/total chlorine measured value and
temperature or pH or ORP measured value
The transmitter has different ways of assigning a relay contact. Switch-on and switch-off
points and pickup and dropout delays can be assigned to the limit contactor. In addition,
you can configure an alarm threshold to output an error message and to start a cleaning
function in conjunction with this.
These functions can be used both for the primary value and for temperature measurement.
Please refer to the switch states in →  36 for a clear illustration of the relay contact
states.
When the measured values increase (maximum function), the relay contact is closed as
of t2 after the switch-on point (t1) has been exceeded and the pickup delay has elapsed
(t2-t1).
The alarm contact switches if the alarm threshold (t3) is reached and the alarm delay
(t4-t3) has also elapsed (errors E067 to E070).
When the measured values decrease, the alarm contact is reset when the value falls
below the alarm threshold (t5) again, as is the relay contact (t7) after the dropout delay
(t7-t6).
If the pickup and dropout delays are set to 0 s, the switch-on and switch-off points are
also switch points of the contacts.
The same settings can also be made for a minimum function in the same way as for the
maximum function.
t
1
t
1
t
2
t
2
t
3
t
3
t
4
t
4
t
5
t
5
t
6
t
6
t
7
t
7
t
t
B
1
2
3
3
2
1
4
5
6
7
4
5
6
7
A
A0025215
 36 Illustration of the alarm and limit value functions
A Switch-on point > switch-off point: Max. function
B Switch-on point < switch-off point: Min. function
1 Alarm threshold
2 Switch-on point
3 Switch-off value
4 Contact ON
5 Alarm ON
6 Alarm OFF
7 Contact OFF
Commissioning Liquisys M CCM223/253
62 Endress+Hauser
P(ID) controller
You can define various controller functions for the transmitter. On the basis of the PID
controller, P, PI, PD and PID controllers can be implemented. For an optimum control
system, use the controller that best suits your application.
P controller
Used for simple linear control purposes with small system deviations. Where major
changes are to be controlled, overshooting may occur. In addition, a lasting control
deviation must be expected.
PI controller
Is used for control systems where overshooting is to be avoided and no lasting control
deviation should occur.
PD controller
Is used for processes that require quick changes and where peaks must be corrected.
PID controller
Is used for processes where a P, PI or PD controller does not control sufficiently.
Configuration options of the P(ID) controller
The following configuration options are available for a PID controller:
Change control gain K
p
(P influence)
Set integral action time T
n
(I influence)
Set derivative action time T
v
(D influence)
Basic load dosing (basic)
You can set a constant dosage amount (field R2411) with basic load dosing (field R241).
PID control plus basic load dosing
If you have selected this function (PID + Basic) in field R241, the PID-controlled dosage
amount does not drop below the basic load value entered in field R2411.
100 %
100 %
A
B
C
A0025221
 37 Control characteristic of PID controller with basic load dosing
A PID plus basic load
B Basic load
C PID
Commissioning
If you do not yet have any experience for setting the control parameters, set the values
that yield the greatest possible stability in the control circuit. Proceed as follows to
optimize the control circuit further:
Increase the control gain K
p
until the controlled variable just starts to overshoot.
Reduce K
p
slightly again and then reduce the integral action time T
n
so that the shortest
possible correction time without overshooting is achieved.
To reduce the response time of the controller, also set the derivative action time T
v
.
Control and fine optimization of the set parameters with a recorder
Liquisys M CCM223/253 Commissioning
Endress+Hauser 63
A
B
A
B
A
B
A
B
A
B
1
2
3
4
5
A0025218
 38 Optimization of settings T
n
and K
p
A Actual value
B Time
1 T
n
too small
2 T
n
too large
3 K
p
too large
4 K
p
too small
5 Optimum setting
Actuating signal outputs via contacts (R247 to R2410 and R257 to R2510)
Each control contact outputs a cyclical signal whose intensity corresponds to the
controller's actuating value. A distinction is made according to the type of signal cycle:
Pulse length modulation
The bigger the calculated manipulated variable is, the longer the contact affected
remains picked up. The period T can be adjusted between 0.5 and 99 s (field R248 or
R258). Outputs with pulse length modulation are used to activate solenoid valves.
Pulse frequency modulation
The bigger the calculated manipulated variable is, the higher the switching frequency of
the contact affected. The maximum switching frequency 1/T can be set between 60 and
180 min
-1
(field R249 or R259). The on-time t
on
is constant. It depends on the set
maximum frequency and is approx. 0.5 s for 60 min
-1
and approx. 170 ms for 180 min
-1
.
170 ms. Outputs with pulse frequency modulation are used to activate directly controlled
solenoid dosing pumps.
Commissioning Liquisys M CCM223/253
64 Endress+Hauser
A
1
0
T
t [s]
A
t [s]
t
1
t
2
t
1
1
0
T
1
T
2
A0025219
 39 Signal of a pulse-length modulated controller contact (left) and of a pulse frequency-modulated controller
contact (right)
Contact: 1 = on, 0 = off T Period
Time (s): t
1
= t
on
t2 = t
off
T1 T2 Impulse period length ( 1/T
1
and 1/T
2
)
Constant controller
The controller can also control the second analog current output (if provided). You can
configure the constant controller in the fields R247 or R257 and O2.
Control characteristic for direct and inverse control action
You can choose between two control characteristics in the R246 and R256 field:
Direct control action = maximum function
Inverse control action = minimum function
X
W
X
W
– X
W
– X
W
100 %
100 %
Y
Y
A
B
A0025222
 40 Control characteristic of a proportional controller with direct and inverse control action
A Direct = maximum function
B Inverse = minimum function
XW Control deviation
Y Current output signal = controller actuating variable
Timer for cleaning function
This function includes a simple cleaning option. You can set the time interval after which
cleaning should start. Therefore you can only select a constant interval sequence.
Other cleaning functions are available for selection in conjunction with the Chemoclean
function (device version with four contacts required, see the "Chemoclean function"
section).
The timer and Chemoclean do not work independently of one another. While one of
the two functions is active, the other cannot be started.
Liquisys M CCM223/253 Commissioning
Endress+Hauser 65
A
B
1
0
t
1
t
2
1
0
t
3
t
t
t
4
t
0
A0025223
 41 Connection between cleaning time, pause time and hold dwell period
A Wiper and/or spray cleaning system
B Hold function
0 Inactive
1 active
t0 Normal operation
t1 cleaning start
t2-t1Cleaning time
t3-t2Clean hold dwell period (0 to 999 s)
t4-t3Pause time between two cleaning intervals (1 to 7200 min)
Chemoclean function
Just like the timer function, Chemoclean can also be used to start a cleaning cycle.
However, Chemoclean also gives you the added option of defining various cleaning and
rinsing intervals and of dosing cleaning agent.
Therefore, it is possible to clean irregularly with different repeat cycles and to separately
set the cleaning times with post rinse times.
Please note the following:
To use the Chemoclean function the transmitter has to be equipped with a designated
relay board (see product structure or chapter "accessories").
The timer and Chemoclean are mutually dependent. While one of the two functions is
active, the other cannot be started.
For the Chemoclean function, the relays 3 (water) and 4 (cleaner) are used.
If the cleaning is prematurely aborted, a post rinse time always follows.
If the setting is "Economy", cleaning only takes place with water.
Commissioning Liquisys M CCM223/253
66 Endress+Hauser
A
B
C
t
0
t
1
t
2
t
3
t
4
t
5
0
0
0
1
1
1
A0025216
 42 Sequence of a cleaning cycle
A Hold function
B Water valve is triggered
C Cleaning valve is triggered
0 Contact off
1 Contact on
t0 Normal operation
t1 cleaning start
t2-t1Pre-rinse time
t3-t2Cleaning time
t4-t3Post rinse time
t5-t4Hold dwell period
Liquisys M CCM223/253 Commissioning
Endress+Hauser 67
Three-point step controller
With this type of controller, you can control motorized valves for metering chlorine gas.
If the controller activates relay 3, the motorized valve closes.
If the controller activates relay 4, the motorized valve opens.
X
W
X < W
X > W
A
B
C
C
B
R4 mark-to-
space ratio
overdosed
underdosed
measuring signal
relay output
R3 mark-to-
space ratio
A0025217-EN
 43 Function of the three-point step controller
A Measured value is in set point window
B Measured value is smaller than the set point
C Measured value is larger than the set point
W Set point
X Measured value
Measured value is in set point window (A)
Relays 3 and 4 are not activated. The motorized valve does not change.
Measured value is smaller than the set point (B)
Not enough chlorine gas is metered. Relay 4 is activated (pulse control). The motorized
valve is opened further and the dosage metered is increased.
Measured value is larger than the set point (C)
Too much chlorine gas is metered. Relay 3 is activated (pulse control). The motorized
valve is closed further and the dosage metered is reduced.
Commissioning Liquisys M CCM223/253
68 Endress+Hauser
Functions marked in italics are not supported by the basic device version.
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
R
RELAY
R
RELAIS
A0009058-EN
Relay contact settings
R1 Select the
contact to be
configured
Rel1
Rel2
Rel3
Rel4
R1
Sel.Relay
Rel1
A0009059-EN
Rel3 (water) and Rel4 (cleaner)
are only available with the
relevant version of the
transmitter.
If Chemoclean is used as the
cleaning method, Rel4 is not
available.
R2 (1) Configure limit
contactor for
Cl
2
/ClO
2
LC PV= limit
contactor
Cl
2
/ClO
2
(1)
LC °C = limit
contactor pH (2)
LC °C = limit
contactor T (3)
PID controller
Cl
2
/ClO
2
(4)
PID controller pH
(5)
Timer (6)
Clean=
Chemoclean (7)
Three-point step
controller
R2
Sel.Type
LC PV
A0009060-EN
PV = process value
If Rel4 is selected in the R1
field, Clean = Chemoclean
cannot be selected. By
confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
R211 Switch function
of R2 (1) off or
on
Off
On
R211
Function
off
A0009067-EN
All the settings are retained.
R212 Enter the
switch-on point
of the contact
20000 ppb
0 to 20000 ppb
20 ppm
0 to 20 ppm
20 (5) mg/l
0 to 20 (5) mg/l
R212
mg/l
On Value
20
A0002033-EN
Never set the switch-on point
and the switch-off point to the
same value! (Only the operating
mode selected in A1 is
displayed.)
R213 Enter the
switch-off point
of the contact
20000 ppb
0 to 20000 ppb
20 ppm
0 to 20 ppm
20 (5) mg/l
0 to 20 (5) mg/l
R213
mg/l
Off Value
20
A0002034-EN
Entering a switch-off point
selects either a Max contact
(switch-off point < switch-on
point) or a Min contact (switch-
off point > switch-on point),
thereby implementing a
hysteresis that is constantly
required (see "Illustration of the
alarm and limit functions"
figure).
Liquisys M CCM223/253 Commissioning
Endress+Hauser 69
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
R214 Enter pickup
delay
0 s
0 to 2000 s
s
R214
On Delay
0
A0009070-EN
R215 Enter dropout
delay
0 s
0 to 2000 s
s
R215
Off Delay
0
A0009071-EN
R216 Enter alarm
threshold (as
absolute value)
20000 ppb
0 to 20000 ppb
20 ppm
0 to 20 ppm
20 (5) mg/l
0 to 20 (5) mg/l
R216
mg/l
A.Thresh
20
A0002038-EN
If the alarm threshold is
undershot/overshot, this
triggers an alarm with the error
message (E067 to E070) and
an error current at the
transmitter (note alarm delay
in field F3).
If defined as a Min contact, the
alarm threshold must be <
switch-off point.
R217 Display status
for limit
contactor
MAX
MIN
R217
LC State
MAX
A0009073-EN
Display only
R2 (2) Configure limit
contactor for pH
or ORP mV
LC pH= limit
contactor pH
LVORP = limit
contactor ORP
mV
R2
Function
LC pH
A0002025-EN
Only for EP version.
Measurement is configured for
pH or ORP depending on the
mode of operation selected in
field B1.
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
R221 Switch function
of R2 (2) off or
on
Off
On
R221
Function
off
A0009074-EN
Any settings made for the limit
contactor are not deleted if the
function is switched off.
R222 Enter the switch-
on point of the
contact
pH 9
pH 4 to 9
1500 mV
0 to 1500 mV
R222
pH
On Value
9.00
A0002041-EN
Never set the switch-on point
and the switch-off point to the
same value!
Commissioning Liquisys M CCM223/253
70 Endress+Hauser
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
R223 Enter the switch-
off point of the
contact
pH 9
pH 4 to 9
1500 mV
0 to 1500 mV
R223
pH
Off Value
9.00
A0002042-EN
Entering a switch-off point
selects either a Max contact
(switch-off point < switch-on
point) or a Min contact (switch-
off point > switch-on point),
thereby implementing a
hysteresis that is constantly
required (see "Illustration of the
alarm and limit functions"
figure).
R224 Enter pickup
delay
0 s
0 to 2000 s
R224
s
On Delay
0
A0009077-EN
R225 Enter dropout
delay
0 s
0 to 2000 s
R225
s
Off Delay
0
A0009078-EN
R226 Enter alarm
threshold (as
absolute value)
pH 9
pH 0 to 9
1500 mV
0 to 1500 mV
R226
pH
A.Thresh
9.00
A0005998-EN
If the alarm threshold is
undershot/overshot, this
triggers an alarm with the error
message (E067 to E070) and
an error current at the
transmitter (note alarm delay
in field F3).
If defined as a Min contact, the
alarm threshold must be <
switch-off point.
R227 Display status
for limit
contactor
MAX
MIN
R227
LC State
MAX
A0009080-EN
Display only
R2 (3) Configure limit
contactor for
temperature
LC °C = limit
contactor T
R2
Sel.Type
LC ¡C
A0009061-EN
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
R231 Switch function
of R2 (3) off or
on
Off
On
R231
Function
off
A0009081-EN
Any settings made for the limit
contactor are not deleted if the
function is switched off.
R232 Enter switch-on
temperature
50 °C
0 to 50 °C
R232
°C
On Value
50.0
A0006003-EN
Never set the switch-on point
and the switch-off point to the
same value!
Liquisys M CCM223/253 Commissioning
Endress+Hauser 71
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
R233 Enter switch-off
temperature
50 °C
0 to 50 °C
R233
¡C
Off Value
50.0
A0002049-EN
Entering a switch-off point
selects either a Max contact
(switch-off point < switch-on
point) or a Min contact (switch-
off point > switch-on point),
thereby implementing a
hysteresis that is constantly
required (see "Illustration of the
alarm and limit functions"
figure).
R234 Enter pickup
delay
0 s
0 to 2000 s
R234
s
On Delay
0
A0002050-EN
R235 Enter dropout
delay
0 s
0 to 2000 s
R235
s
Off Delay
0
A0002051-EN
R236 Enter alarm
threshold (as
absolute value)
50 °C
0 to 50 °C
R236
¡C
A.Thresh
50.0
A0002052-EN
If the alarm threshold is
undershot/overshot, this
triggers an alarm with the error
message (E067 to E070) and
an error current at the
transmitter (note alarm delay
in field F3).
If defined as a Min contact, the
alarm threshold must be <
switch-off point.
R237 Display status
for limit
contactor
MAX
MIN
R237
LC State
MAX
A0002053-EN
Display only
R2 (4) Configure P(ID)
controller for
Cl
2
/ClO
2
PIDPV
R2
Function
PIDPV
A0002027-EN
PV = process value of main
measuring parameter
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
R241 Switch function
of R2 (4) off or
on
Off
On
Basic
PID+B
R241
Function
Off
A0002054-EN
On = PID controller
Basic = basic load dosing
PID+B = PID controller + basic
load dosing
R242 Enter set point 500 ppb
0 to 20000 ppb
0.5 ppm
0 to 20 ppm
0.5 (0.1) mg/l
0 to 20 (5) mg/l
R242
mg/l
Setpoint
0.50
A0002057-EN
The set point is the value to be
maintained by the control
system. Using this control
process, this value is restored
when an upwards or
downwards deviation occurs.
Commissioning Liquisys M CCM223/253
72 Endress+Hauser
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
R243 Enter control
gain K
P
1.00
0.01 to 20.00
R243
Kp
1.00
A0002058-EN
See the "P(ID) controller"
section.
R244 Enter integral
action time T
n
(0.0 = no I-
component)
0.0 min
0.0 to 999.9 min
R244
min
Time Tn
0.0
A0002059-EN
See the "P(ID) controller"
section.
With every hold, the I-
component is set to zero.
Although the hold can be
deactivated in field S2, this
does not apply for Chemoclean
and timer!
R245 Enter derivative
action time T
v
(0.0 = no D-
component)
0.0 min
0.0 to 999.9 min
R245
min
Time Tv
0.0
A0002060-EN
See the "P(ID) controller"
section.
R246 Select controller
characteristic
Inv = inverse
(initial setting
for sodium
hypochlorite
Dir = direct
R246
Direction
inv
A0002061-EN
See the "P(ID) controller"
section.
This setting is required
depending on the desired
dosing direction (dosing above
or below the set point).
R247 Select pulse
length or pulse
frequency
Len = pulse
length
Freq = pulse
frequency
Curr = current
output 2
R247
Oper.Mode
len
A0002062-EN
Pulse length e.g. for solenoid
valve, pulse frequency e.g. for
solenoid dosing pump, see the
"Actuating signal outputs"
section.
Curr = current output 2 can
only be selected if O2 = Contr.
R248 Enter pulse
interval
10.0 s
0.5 to 999.9 s
R248
s
PulsePer.
10.0
A0002063-EN
This field only appears if pulse
length is selected in R247.
If pulse frequency is selected,
R248 is skipped and entries
continue with R249.
R249 Enter maximum
pulse frequency
of the adjuster
120 min
-1
60 to 180 min
-1
R249
1/min
Max.PFreq
120
A0002064-EN
This field only appears if pulse
frequency is selected in R247. If
pulse length is selected, R249 is
skipped and entries continue
with R2410.
R2410 Enter minimum
switch-on time
t
ON
0.3 s
0.1 to 5.0 s
R2410
s
Min.PTime
0.3
A0002055-EN
This field only appears if pulse
length is selected in R247.
Liquisys M CCM223/253 Commissioning
Endress+Hauser 73
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
R2411 Enter basic load 0 %
0 to 40 %
R2411
%
BasicLoad
0
A0002056-EN
When you select the basic load,
you enter the desired dosing
quantity.
100% basic load would
correspond to:
Constantly on if R247 = len
Fmax if R247 = freq (field
R249)
20 mA if R247 = curr
R2 (5) Configure P(ID)
controller for pH
PIDpH
R2
Function
PIDpH
A0002028-EN
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
R251 Switch function
of R2 (5) off or
on
Off
On
Basic
PID+B
R251
Function
Off
A0002084-EN
On = PID controller
Basic = basic load dosing
PID+B = PID controller + basic
load dosing
R252 Enter set point pH 7.20
pH 4 to 9
R252
pH
Setpoint
7.20
A0002087-EN
The set point is the value to be
maintained by the control
system. Using this control
process, this value is restored
when an upwards or
downwards deviation occurs.
R253 Enter control
gain K
P
1.00
0.01 to 100.00
R253
Kp
1.00
A0002088-EN
See the "P(ID) controller" section
R254 Enter integral
action time T
n
(0.0 = no I-
component)
0.0 min
0.0 to 999.9 min
R254
min
Time Tn
0.0
A0002089-EN
See the "P(ID) controller" section
With every hold, the I-
component is set to zero.
Although the hold can be
deactivated in field S2, this
does not apply for Chemoclean
and timer!
R255 Enter derivative
action time T
v
(0.0 = no D-
component)
0.0 min
0.0 to 999.9 min
R255
min
Time Tv
0.0
A0002090-EN
See the "P(ID) controller" section
R256 Select controller
characteristic
Inv = inverse
Dir = direct
(Initial setting for
acid)
R256
Direction
dir
A0002091-EN
See the "P(ID) controller" section
This setting is required
depending on the desired
dosing direction (dosing above
or below the set point).
Commissioning Liquisys M CCM223/253
74 Endress+Hauser
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
R257 Select pulse
length or pulse
frequency
Len = pulse
length
Freq = pulse
frequency
Curr = current
output 2
R257
Oper.Mode
len
A0002092-EN
Pulse length e.g. for solenoid
valve
Pulse frequency e.g. for
solenoid dosing pump
Curr = current output 2 can
only be selected if O2 = Contr.
R258 Enter pulse
interval
10.0 s
0.5 to 999.9 s
R258
s
PulsePer.
10.0
A0002093-EN
This field only appears if pulse
length is selected in R257.
If pulse frequency is selected,
R258 is skipped and entries
continue with R259.
R259 Enter maximum
pulse frequency
of the adjuster
120 min
-1
60 to 180 min
-1
R259
1/min
Max.PFreq
120
A0002094-EN
This field only appears if pulse
length is selected in R257.
If pulse length is selected, R259
is skipped and entries continue
with R2510.
R2510 Enter minimum
switch-on time
t
ON
0.3 s
0.1 to 5.0 s
R2510
s
Min.PTime
0.3
A0002085-EN
This field only appears if pulse
length is selected in R257.
R2511 Enter basic load 0 %
0 to 40 %
R2511
%
BasicLoad
0
A0002086-EN
This field only appears for the
EP version.
When you select the basic load,
you enter the desired dosing
quantity.
100% basic load would
correspond to:
Constantly on if R257 = len
F
max
if R257 = freq (field
R259)
20mA if R257 = curr
R2 (6) Configure
cleaning
function (timer)
Timer (6)
R2
Sel.Type
Timer
A0009063-EN
Only one cleaning agent
(generally water) is used for the
cleaning.
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
R261 Switch function
of R2 (6) off or
on
Off
On
R261
Function
Off
A0002095-EN
R262 Enter rinsing/
cleaning time
30 s
0 to 999 s
R262
s
RinseTime
30
A0002096-EN
Settings for hold and relay are
active for this time.
Liquisys M CCM223/253 Commissioning
Endress+Hauser 75
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
R263 Enter pause time 360 min
1 to 7200 min
R263
min
PauseTime
360
A0002097-EN
The pause time is the time
between two cleaning cycles
(see the "Timer for cleaning
function" section).
R264 Enter minimum
pause time
120 min
1 to 3600 min
R264
min
Min.Pause
120
A0002098-EN
The minimum pause time
prevents constant cleaning if a
cleaning trigger is pending.
R2 (7) Configure
cleaning with
Chemoclean (for
version with four
contacts,
Chemoclean
option and
contacts 3 and 4
assigned)
Clean=
Chemoclean (7)
R2
Sel.Type
Clean
A0009064-EN
See the "Chemoclean function"
section.
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
R271 Switch function
of R2 (7) off or
on
Off
On
R271
Function
Off
A0002099-EN
R272 Select type of
start pulse
Int = internal
(time-
controlled)
Ext = external
(digital input 2)
I+ext = internal +
external
I+stp = internal,
suppressed by
external
R272
CleanTrig
int
A0002100-EN
No real time clock is available.
External suppression is required
for irregular time intervals (e.g.
weekends).
R273 Enter pre-rinse
time
20 s
0 to 999 s
R273
s
PreRinse
20
A0002101-EN
Rinsing is performed with
water.
R274 Enter cleaning
time
10 s
0 to 999 s
R274
s
CleanTime
10
A0002102-EN
Cleaning is performed with
cleaning agent and water.
R275 Enter post rinse
time
20 s
0 to 999 s
R275
s
PostRinse
20
A0002103-EN
Rinsing is performed with
water.
Commissioning Liquisys M CCM223/253
76 Endress+Hauser
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
R276 Enter number of
repeat cycles
0
0 to 5
R276
Rep. Rate
0
A0002104-EN
R273 to R275 is repeated.
R277 Enter pause time 360 min
1 to 7200 min
R277
min
PauseTime
360
A0002105-EN
The pause time is the time
between two cleaning cycles
(see the "Chemoclean function"
section).
R278 Enter minimum
pause time
120 min
1 to R277
R278
min
Min.Pause
120
A0002106-EN
The minimum pause time
prevents constant cleaning if an
external cleaning start is
pending.
R279 Enter number of
cleaning cycles
without cleaning
agent (economy
function)
0
0 to 9
R279
EconomyCl
0
A0002107-EN
After cleaning with cleaner, up
to 9 cleaning sessions can be
carried out with water only
until the next cleaning session
with cleaner takes place.
R2 (8) Configure three-
point step
controller for
Cl
2
/ClO
2
3 PSt (8)
R2
Function
3PSt
A0002031-EN
Only with relays 3 and 4..
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
R281 Switch function
of R2 (8) off or
on
Off
On
R281
Function
Off
A0002108-EN
R282 Enter set point 500 ppb
0 to 20000 ppb
0.5 ppm
0 to 20 ppm
0.5 (0.1) mg/l
0 to 20 (5) mg/l
R282
mg/l
Setpoint
0.50
A0002109-EN
The set point is the value to be
maintained by the control
system. Using this control
process, this value is restored
when an upwards or
downwards deviation occurs.
R283 Enter control
gain K
P
1.00
0.10 to 100.00
R283
Kp
1.00
A0002110-EN
See the "P(ID) controller" section
R284 Enter integral
action time T
n
0.0 min
0.0 to 999.9 min
R284
min
Time Tn
0.0
A0002111-EN
See the "P(ID) controller" section
Liquisys M CCM223/253 Commissioning
Endress+Hauser 77
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
R285 Enter minimum
switch-on time
t
ON
0.3 s
0.1 to 5.0 s
R285
s
Min.PTime
0.3
A0002112-EN
R286 Enter motor run
time
60 s
10 to 999 s
R286
s
MotorTime
60
A0002113-EN
Motor run time from "fully
closed" state to "fully open"
state.
R287 Enter neutral
zone
10 %
0 to 40 %
R287
%
NeutrZone
10
A0002114-EN
7.4.8 Service
Coding Field Range of
adjustment
(factory settings in
bold)
Display Info
S
SERVICE
function group
S
SERVICE
A0008408-EN
Service function settings.
S1 Select language ENG = English
GER = German
FRA = French
ITA = Italian
NL = Dutch
ESP = Spanish
S1
Language
ENG
A0008409-EN
The option selected only
applies for the fault-
signaling contact, not for the
error current.
S2 Configure a hold S+C = hold during
configuration and
calibration
Cal = hold during
calibration
Setup = hold during
configuration
None = no hold
S2
Auto HOLD
S+C
A0008413-EN
S = setup
C = calibration
S3 Manual hold Off
On
S3
Man. HOLD
off
A0008414-EN
The setting is retained even
in the event of a power
failure.
Commissioning Liquisys M CCM223/253
78 Endress+Hauser
Coding Field Range of
adjustment
(factory settings in
bold)
Display Info
S4 Enter hold dwell
period
10 s
0 to 999 s
S4
s
Cont.Time
10
A0008415-EN
S5 Enter SW
upgrade release
code (Plus
Package)
0000
0000 to 9999
S5
0000
PlusCode
A0008416-EN
The code can be found on the
nameplate.
If an incorrect code is
entered, you are taken back
to the measurement menu.
The number is edited with
the PLUS or MINUS key and
confirmed with the ENTER
key. "1" is displayed if the
code is active.
S6 Enter SW
upgrade release
code for
Chemoclean
0000
0000 to 9999
S6
CleanCode
0000
A0008417-EN
The code can be found on the
nameplate.
If an incorrect code is
entered, you are taken back
to the measurement menu.
The number is edited with
the PLUS or MINUS key and
confirmed with the ENTER
key. "1" is displayed if the
code is active.
S7 Order number is
displayed
S7
EK0005
order
A0006005
If the device is upgraded, the
order code is changed
automatically.
S8 Serial number is
displayed
S8
12345678
SerNo
A0008420-EN
S9 Reset the device
to the basic
settings
No
Sens = sensor data
Facty = factory
settings
S9
S.Default
no
A0008421-EN
Sens = last calibration is
deleted and is reset to factory
setting.
Facty = all data (apart from
A1 and S1) are deleted and
reset to the factory setting!
S10 Perform device
test
No
Displ = display test
S10
Test
no
A0008410-EN
Liquisys M CCM223/253 Commissioning
Endress+Hauser 79
7.4.9 E+H Service
Coding Field Range of adjustment
(factory settings in
bold)
Display Info
E
E+H SERVICE
function group
E
E+H SERV
A0007857-EN
Information on the
device version
E1 Select module Contr = controller
(central module) (1)
Trans = transmitter (2)
Main = power unit (3)
Rel = relay module (4)
Sens = sensor (5)
E1
Select
Contr
A0007858-EN
E111
E121
E131
E141
E151
Software version is
displayed
E111
SW-Vers.
xx.xx
A0007859-EN
If E1 = contr: device
software
If E1 = trans, main, rel:
module firmware
If E1 = sens: sensor
software
E112
E122
E132
E142
E152
Hardware version
is displayed
E112
HW-Vers.
xx.xx
A0007861-EN
Info display
E113
E123
E133
E143
E153
Serial number is
displayed
E113
12345678
SerNo
A0007860-EN
Info display
E114
E124
E134
E144
E154
Module ID is
displayed
E114
Modul-ID
LSG
A0007862-EN
Info display
Commissioning Liquisys M CCM223/253
80 Endress+Hauser
7.4.10 Interfaces
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
I
INTERFACE
function group
I
INTERFACE
A0007863-EN
Communication settings (only
for HART or PROFIBUS device
version).
I1 Enter bus
address
Address
HART: 0 to 15
or
PROFIBUS: 0 to
126
I1
Address
126126
A0007864-EN
Each address may only be
assigned once in a network. If a
device address ≠ 0 is selected for
a HART device, the current
output is automatically set to 4
mA and the device prepares for
multi-drop operation.
I2 The tag name is
displayed
I2
@@@@@@@@
Tag
A0007865-EN
7.4.11 Communication
For devices with a communication interface, please also refer to the separate Operating
Instructions BA00208C/07/EN (HART®) or BA00209C/07/DE (PROFIBUS®).
Liquisys M CCM223/253 Commissioning
Endress+Hauser 81
7.5 Calibration
Use the CAL key to access the calibration function group.
Use this function group to calibrate the transmitter.
When calibrating the "Free chlorine" measurement mode, make sure to pay attention
to the pH value and the temperature of the medium. The limit values are provided in
the following table:
Sensor pH
min
pH
max
T
min
T
max
CCS140 4 8 10 °C (50 °F) 45 °C (113 °F)
CCS141 4 8.2 2 °C (36 °F) 45 °C (113 °F)
CCS240 - - 2 °C (36 °F) 45 °C (113 °F)
CCS241 - - 2 °C (36 °F) 45 °C (113 °F)
CCS120 5.5 9.5 5 °C (41 °F) 45 °C (113 °F)
Please note the following:
You require a photometer, e.g. PF-3 (see "Accessories") to calibrate chlorine and chlorine
dioxide. A photometer with a higher accuracy rating and lower detection limit is required
for calibration in the trace range (<0.1 mg/l).
If the calibration is aborted by simultaneously pressing the PLUS and MINUS keys
(return to C15, C29 or C35), or if the calibration is incorrect, the original calibration data
are used again. A calibration error is indicated by “ERR” and the sensor symbol flashes
on the display.
Repeat calibration!
For each calibration, the device automatically switches to hold (factory setting).
On completion of the calibration, the device returns to the measurement mode. The
"hold" symbol appears on the display during the hold dwell period (field S4).
Coding Field Range of
adjustment
(factory
settings in
bold)
Display Info
C(1)
CALIBRATION
function group:
Calibration Cl
2
/
ClO
2
Cl2
ClO2
C
CALIBRAT
Cl2
A0006351-EN
Cl2 if A1 = 120/140/141/963
ClO2 if A1 = 240/241
C11 Enter DPD
calibration value
Value of last
calibration
C11
mg/l
DPD value
0.50
A0002420-EN
Minimum values for the
calibration:
For CCS120/140/240 and
sensor 963: 0.05 mg/l
For CCS141/241: 0.01 mg/l
C12 Zero point
calibration?
No
Yes
C12
Zero cal
no
A0002421-EN
Only if A1 = 963
Zero point calibration:
1. Pass unchlorinated water
through the assembly.
2. Wait for 10 minutes.
3. Accept by selecting YES and
pressing ENTER
Commissioning Liquisys M CCM223/253
82 Endress+Hauser
Coding Field Range of
adjustment
(factory
settings in
bold)
Display Info
C13 Slope is displayed 100 %
Minimum 25%
(3%)
Maximum
500%
C13
%
Slope
100
A0002422-EN
Minimum permitted slope:
For CCS140/141 with pH
compensation and for
CCS240/241: 25%
For CCS120/140/141 without
pH compensation and for
sensor 963: 3%
C14 Calibration status
is displayed
o. k.
E xxx
C14
Status
o.k.
A0002423-EN
C15 Store calibration
result
Yes
No
New
C15
Store
yes
A0002424-EN
If C14 = E xxx, then only No or
New. If New, then return to C.
If Yes/No, then return to
"Measurement".
C(2)
CALIBRATION
function group:
pH calibration
pH
C
CALIBRAT
pH
A0002418-EN
C21 Calibration status
is displayed
25 °C
0 to 50 °C
C21
¡C
MTC-Temp
25.0
A0002425-EN
This field is only for recording
the calibration temperature. An
entry must not be made.
C22 Enter pH value of
the first buffer
solution
Buffer value of
the last
calibration
pH 3.50 to 9.50
C22
pH
Buffer 1
7.00
A0002427-EN
Press the ENTER key to display
the current measured value.
Press the ENTER key again as
soon as the measured value has
adjusted to the buffer value.
C23 Calibration is
performed
C23
pH
Buffer 1
7.00
A0002428-EN
Stability check:
The value is accepted if the
stability level is ≤pH ±0.05 for
more than 10 seconds.
C24 Enter pH value of
the second buffer
solution
Buffer value of
the last
calibration
pH 3.50 to 9.50
C24
pH
Buffer 2
4.00
A0002429-EN
Buffer 2 must have a different
value to buffer 1. A plausibility
check is performed.
Press the ENTER key and
proceed as in field C22.
C25 Calibration is
performed
C25
pH
Buffer 2
4.00
A0002430-EN
Stability check:
The value is accepted if the
stability level is ≤pH ±0.05 for
more than 10 seconds.
Liquisys M CCM223/253 Commissioning
Endress+Hauser 83
Coding Field Range of
adjustment
(factory
settings in
bold)
Display Info
C26 Slope is displayed 59.16 mV/pH
38.00 to 65.00
mV/pH
C26
mV/pH
Slope
59.16
A0002431-EN
C27 Zero point is
displayed
pH 7.00
pH 5.00 to 9.00
C27
pH
Zero
7.00
A0002432-EN
C28 Calibration status
is displayed
o. k.
E xxx
C28
Status
o.k.
A0002452-EN
C29 Store calibration
result?
Yes
No
New
C29
Store
yes
A0002434-EN
If C28 = E xxx, then only No or
New. If New, then return to C.
If Yes/No, then return to
"Measurement".
C(3)
CALIBRATION
function group:
ORP mV
calibration
ORPmV
C
CALIBRAT
ORPmV
A0002419-EN
C31 Enter the value of
the ORP buffer
Buffer value of
the last
calibration
0 to 1500 mV
C31
mV
mV Buffer
225
A0002435-EN
Press the ENTER key to display
the current measured value.
Press the ENTER key again as
soon as the measured value has
adjusted to the buffer value.
C32 Calibration is
performed
C32
mV
CAL mV
225
A0002436-EN
Stability check:
The value is accepted if the
stability level is ≤pH ± 1 mV for
more than 10 seconds.
C33 Zero point is
displayed
-100 to +100
mV
C33
mV
Zero
0
A0002437-EN
C34 Calibration status
is displayed
o. k.
E xxx
C34
Status
o.k.
A0002438-EN
Commissioning Liquisys M CCM223/253
84 Endress+Hauser
Coding Field Range of
adjustment
(factory
settings in
bold)
Display Info
C35 Store calibration
result?
Yes
No
New
C35
Store
yes
A0002439-EN
If C34 = E xxx, then only No or
New. If New, then return to C.
If Yes/No, then return to
"Measurement".
C(4)
CALIBRATION
function group:
Zero point
CCS120
Zero point
C
CALIBRAT
Zero
A0006376-EN
Zero point calibration for
CCS120
C12 Zero point
calibration?
No
Yes
C12
Zero cal
no
A0002421-EN
Only if A1 = 120
Zero point calibration:
1. Pass unchlorinated water
through the assembly.
2. Wait for 10 minutes.
3. Accept by selecting YES and
pressing ENTER
C14 Calibration status
is displayed
o. k.
E xxx
C14
Status
o.k.
A0002423-EN
C15 Store calibration
result?
Yes
No
New
C15
Store
yes
A0002424-EN
If C14 = E xxx, then only No or
New. If New, then return to C.
If Yes/No, then return to
"Measurement".
Liquisys M CCM223/253 Diagnostics and troubleshooting
Endress+Hauser 85
8 Diagnostics and troubleshooting
8.1 Trouble shooting instructions
The transmitter continuously monitors its functions itself. If an error occurs which the
device recognizes, this is indicated on the display. The error number is shown below the
display of the main measured value. If more than one error occurs, you can call these up
with the MINUS key.
Refer to the "System error messages" table for the possible error numbers and remedial
measures.
Should a malfunction occur without any transmitter error message, please refer to the
"Process-specific errors" or the "Device-specific errors" tables to localize and rectify the error.
These tables provide you with additional information on any spare parts required.
8.2 System error messages
You can display and select the error messages with the MINUS key.
Error
No.
Display Tests/remedial action Alarm
contact
Error
current
Autom.
cleaning
start
PROFIBU
S
Status
Facty Facty Facty PV
1)
User User User Temp
E001 EEPROM memory
error
Switch off device and
switch it on again.
Load software
compatible with
hardware
Load measurement-
parameter specific
device software.
If the error persists,
send in the device for
repair to your local
sales center or replace
the device.
Yes No X 0C
X 0C
E002 Device not calibrated,
calibration data
invalid, no user data or
user data invalid
(EEPROM error),
device software not
suitable for hardware
(controller)
Yes No X 0C
X 0C
E003 Download error Invalid configuration.
Repeat download.
Yes No X 0C
X 0C
E004 Device software
version not compatible
with module hardware
version
Load software compatible
with hardware
Load measurement-
parameter specific device
software.
Yes No X 0C
X 0C
E007 Transmitter
malfunction, device
software not
compatible with
transmitter version
Yes No X 0C
X 0C
E010 Temperature sensor
defective, not
connected or short-
circuited
(measurement
continues with 25 °C)
Check temperature sensor
and connections; check
the measuring device and
measuring cable with a
temperature simulator if
necessary.
Yes No No 80
0C
E032 Upper or lower pH
slope range exceeded
Repeat calibration and
replace buffer solution; if
necessary, replace sensor
and check the device and
No No X 80
X 80
E033 pH value zero point too
low or too high
No No X 80
Diagnostics and troubleshooting Liquisys M CCM223/253
86 Endress+Hauser
Error
No.
Display Tests/remedial action Alarm
contact
Error
current
Autom.
cleaning
start
PROFIBU
S
Status
Facty Facty Facty PV
1)
User User User Temp
measuring cable with a
simulator.
X 80
E034 ORP offset range
exceeded or below
range
No No X 80
X 80
E035 Sensor 963 zero point
signal outside
permitted range
Service the sensor (in
accordance with sensor
manual).
Check connections.
Check activated carbon
filter.
No No X 80
X 80
E038 Cl sensor signal
outside permitted
range during slope
calibration
Service the sensor (in
accordance with sensor
manual).
Check connections.
Check DPD measuring
device.
Do not use organic
chlorination agent.
No No X 80
X 80
E041 Calculation of
calibration parameters
aborted
Repeat calibration and
replace buffer solution;
replace sensor if
necessary, check device
and measuring cable.
No No X 80
X 80
E042 Distance between
buffer value and zero
point (pH7) too small
(single-point
calibration)
For slope calibration, use
a buffer solution which
has at least a distance of
ΔpH = 2 to the electrode
zero point.
No No X 80
X 80
E043 Distance between
buffer 1 and buffer 2
calibration values too
small (two-point
calibration)
Use buffer solutions
which differ by at least
Δ pH = 2.
No No X 80
X 80
E044 Stability requirement
not met during
calibration
Repeat calibration and
replace buffer solution; if
necessary, replace sensor
and check the device and
measuring cable with a
simulator.
No No X 80
X 80
E045 Calibration aborted No No X 80
X 80
E055 Lower Cl/ClO
2
measuring range
exceeded
Check measurement and
connections; if necessary,
check device and
measuring cable with a
simulator.
Yes No No 44
80
E056 Lower pH/mV
measuring range
exceeded
Yes No No 44
80
E057 Upper Cl/ClO
2
measuring range
exceeded
Yes No No 44
80
E058 Upper pH/mV
measuring range
exceeded
Yes No No 44
80
E059 Below temperature
measuring range
Yes No No 80
44
Liquisys M CCM223/253 Diagnostics and troubleshooting
Endress+Hauser 87
Error
No.
Display Tests/remedial action Alarm
contact
Error
current
Autom.
cleaning
start
PROFIBU
S
Status
Facty Facty Facty PV
1)
User User User Temp
E061 Temperature
measuring range
exceeded
Yes No No 80
44
E063 Below current output
range 1
Check measured value
and current assignment
Yes No No 80
80
E064 Current output range 1
exceeded
Yes No No 80
80
E065 Below current output
range 2
Yes No No 80
80
E066 Current output range 2
exceeded
Yes No No 80
80
E067 Set point exceeded
limit contactor 1
Check configuration Yes No No 80
80
E068 Set point exceeded
limit contactor 2
Yes No No 80
80
E069 Set point exceeded
limit contactor 3
Yes No No 80
80
E070 Set point exceeded
limit contactor 4
Yes No No 80
80
E080 Current output 1 range
too small
Increase range in "Current
outputs" menu.
Yes No X 80
X 80
E081 Current output 2 range
too small
Yes No X 80
X 80
E085 Incorrect setting for
error current
If the current range "0 to
20 mA" was selected in
field O311, the error
current may not be set to
"2.4 mA".
Yes No No 80
80
E100 Current simulation
active
Yes No X 80
X 80
E101 Service function active Switch off service function
or switch device off and
then on again.
No No X 80
X 80
E102 Manual mode active No No X 80
X 80
E106 Download active Wait for download to
finish.
No No X 80
X 80
E116 Download error Repeat download. Yes No X 0C
X 0C
E152 Measuring signal of
Cl/ClO
2
parameter
delayed or frozen
Check and service the
sensor and connection,
and replace if
necessary.
No No No 44
44
Diagnostics and troubleshooting Liquisys M CCM223/253
88 Endress+Hauser
Error
No.
Display Tests/remedial action Alarm
contact
Error
current
Autom.
cleaning
start
PROFIBU
S
Status
Facty Facty Facty PV
1)
User User User Temp
E153 Measuring signal of
pH/mV parameter
delayed or frozen
Check whether medium
has really changed or
not.
No No No 44
44
E154 Cl/ClO
2
below lower
alarm threshold for
period exceeding
alarm delay
Perform manual
comparison
measurement if
necessary.
Service the sensor (in
accordance with sensor
manual).
Recalibrate the
measuring system.
Check the flow.
Check the chemical
supply.
Check dosing devices.
Yes No No X
X
E155 Cl/ClO
2
above upper
alarm threshold for
period exceeding
alarm delay
Yes No No X
X
E156 Actual Cl/ClO
2
value
undershoots alarm
threshold for longer
than the set
permissible maximum
period
Yes No No X
X
E157 Actual Cl/ClO
2
value
exceeds alarm
threshold for longer
than the set
permissible maximum
period
Yes No No X
X
E158 pH/mV below lower
alarm threshold for
period exceeding
alarm delay
Yes No No X
X
E159 pH/mV above upper
alarm threshold for
period exceeding
alarm delay
Yes No No X
X
E160 Actual pH/mV value
undershoots alarm
threshold (CC
setpoint) for longer
than the set
permissible maximum
period
Yes No No X
X
E161 Actual pH/mV value
exceeds alarm
threshold (CC
setpoint) for longer
than the set
permissible maximum
period
Yes No No X
X
E162 Dosage stop Check settings in the
CURRENT INPUT and
CHECK function groups.
Yes No No X
X
E163 Uncompensated
chlorine value too
imprecise since pH
value > 9
Check pH value and adjust
according to system
requirements. If pH values
> 9, the disinfection effect
is questionable since the
chlorine now exists as the
less effective OCl
-
.
Yes No No X
X
Liquisys M CCM223/253 Diagnostics and troubleshooting
Endress+Hauser 89
Error
No.
Display Tests/remedial action Alarm
contact
Error
current
Autom.
cleaning
start
PROFIBU
S
Status
Facty Facty Facty PV
1)
User User User Temp
E170 Flow through
assembly too low or
zero
Restore flow. Check
medium pipe.
Yes No No X
X
E171 Flow in main stream
too low or zero
Restore flow. Yes No No X
X
E172 Switch-off limit for
current input exceeded
Check process variables at
sending measuring device.
Change range assignment
if necessary.
Yes No No X
X
E173 Current input < 4 mA Yes No No X
X
E174 Current input > 20 mA Yes No No X
X
1) PV = process variable, primary value
8.3 Process-specific errors
Use the following table to localize and rectify any errors occurring.
Error Possible cause Tests/remedial action Tools, spare parts
No device function Device fuse defective Replace fuse Fine-wire fuse, M 250 V /
3.15 A
No power supply Establish power supply Check with voltmeter
Display flashes Automatic controller
switch-off due to alarm
Determine cause according to
error code Exxx and eliminate.
Current output simulation End the simulation
Chlorine
measurement:
Slope too low
Sensor was in chlorine-
free water or in air.
Short conditioning over (not in!)
chlorine bleach, wait for
conditioning time in water
before calibration.
Chlorine bleach / chlorine
parent solution
No match with
DPD control
measurement
Measurement takes place
without pH compensation,
while DPD measurement is
always buffered to pH 6.3.
Measure chlorine value pH-
compensated
Select CCM223/253 with
ES option (manual
compensation) or EP
(automatic compensation).
DPD measured
value much too
high
Organic chlorination agent
used (may also be used
only at times or for shock
chlorination). In this case,
no correlation between
actual free chlorine, DPD
measurement and
amperometric
measurement. DPD value
too high by a factor of up
to 5.
Use free (gaseous) chlorine or
chlorine from inorganic chlorine
compounds.
If organic chlorination
agent was used previously,
the entire system must be
evacuated and carefully
cleaned!
Chlorine value too
high
Membrane defective Replace membrane cap. Replacement cartridges
CCY 14-WP
Polarization not complete Wait for polarization time to
finish
Be patient
Foreign oxidizing agent Analyze medium Detailed knowledge of the
process
Diagnostics and troubleshooting Liquisys M CCM223/253
90 Endress+Hauser
Error Possible cause Tests/remedial action Tools, spare parts
Shunt in chlorine sensor Replace sensor Replacement sensor
Chlorine value too
low
Measuring chamber not
closed
Refill and screw closed carefully Electrolyte
Air cushion outside in
front of membrane
Remove air bubble, possibly
select better installation
position
Air cushion inside
membrane
Refill and screw closed so that it
is bubble-free
Electrolyte
Chlorine value
wrong/cannot be
calibrated; zero
current too large
Wrong polarization
voltage
Measure polarization voltage,
replace MKC1 module if
necessary.
DVM (+) at S or 90, DVM
(-) at 91
CCS140/141: -20 mV
CCS240/241: +120 mV
Wrong sensor type
selected
Check sensor selection
pH/mV
measurement:
Measuring chain
zero-point cannot
be adjusted
Contaminated reference
system
Test with new sensor pH/mV sensor
Membrane clogged Clean or grind membranes (not
with TEFLON® membranes)
HCl 3%, needle file (only
file in one direction); new
sensor
Measuring line open Short-circuit pH input and
connect to PM -> reading pH 7
Asymmetric sensor
voltage too high
Clean junction or test with
another sensor
HCl 3%, needle file (only
file in one direction); new
sensor
Potential matching of
Liquisys -> medium
incorrect
Always connect CCM223/253
symmetrically with PM.
Wiring diagrams
No or slow change
of readings
Sensor fouled Clean sensor Cleaning agent
Sensor old Replace sensor New sensor
Sensor defective
(reference lead)
Replace sensor New sensor
Measuring chain
slope not
adjustable/
slope too low
Connection not at high
impedance
(moisture, dirt)
Check cable, plug connector and
junction boxes
pH simulator, insulation
tester
Device input defective pH measurement directly at
device
pH simulator
Sensor old Replace sensor pH sensor
Measuring chain
slope not
adjustable/
No slope
Hair-line crack in the glass
membrane
Replace sensor pH sensor
Connection not at high
impedance
Check cable, plug connector and
junction boxes
pH simulator, insulation
tester
Constant, incorrect
measured value
Sensor does not immerse
properly or protection cap
not removed
Check installation position,
remove protection cap
Air pockets in assembly Check assembly and installation
position
Grounding short at or in
device
Perform test measurement in
insulated vessel, perform with
buffer solution if required.
Plastic vessel, buffer
solutions
Hair-line crack in the glass
membrane
Replace sensor pH sensor
Liquisys M CCM223/253 Diagnostics and troubleshooting
Endress+Hauser 91
Error Possible cause Tests/remedial action Tools, spare parts
Device in impermissible
operating condition (does
not respond when key
pressed)
Disconnect line voltage for
approx. 10 seconds
Possibly EMC problem: if
problem persists, check
grounding and wire
routing.
Incorrect
temperature value
Incorrect sensor
connection
Check connections using wiring
diagram. Three-wire connection
always required
Wiring diagram in
"Electrical connection"
section
Sensor or measuring cable
defective
Check sensor and cable Ohmmeter
Incorrect pH
measured value in
the process
Flow too high Reduce flow or measure in a
bypass.
Potential in medium Possibly ground with or/at PM
pin (connect PA/PM with PE).
Problem mainly occurs in
plastic lines.
Sensor fouling or buildup
on sensor
Clean sensor For heavily contaminated
media: use spray cleaning
Fluctuations in
measured value
Interference on measuring
cable
Connect cable shield as per
wiring diagram
See the "Electrical
connection" section
Interference on signal
output cable
Check cable routing, possibly
route cable separately
Route signal output and
measuring input lines
separately
Interference potential in
medium
Eliminate source of interference
or ground medium as close as
possible to sensor.
No potential matching on
symmetrical input
Connect PM pin in assembly to
device terminal PA/PM.
Controller or timer
cannot be
activated
No relay module available Install LSR1-2 or LSR1-4
module
Controller/limit
contact does not
work
Controller switched off Activate controller See fields R2xx
Controller in operating
mode "Manual off"
Select "Auto" or "Manual on"
mode
Keyboard, REL key
Pickup delay setting too
long
Switch off or shorten pickup
delay time
See fields R2xx
"Hold" function active “Auto hold” for calibration,
“Hold” input activated;
“Hold” active via keyboard
See fields S2 to S4
Controller/limit
contact works
continuously
Controller in operating
mode "Manual on"
Select "Auto" or "Manual off"
mode
Keyboard, REL and AUTO
keys
Dropout delay setting too
long
Shorten dropout delay time See fields R2xx
Control loop interruption Check measured value, current
output value, actuators,
chemical supply
No current output
signal
Cable disconnected or
short-circuited
Disconnect cable and measure
directly at device
mA meter 0–20 mA
Output defective See the "Device-specific errors"
section
Fixed current
output signal
Current simulation active Switch off simulation. See field O3
Impermissible operating
state of processor system
Disconnect line voltage for
approx. 10 seconds
Possibly EMC problem: if
problem persists, check
grounding and wire
routing.
Incorrect current
output signal
Incorrect current
assignment
Check current assignment: 0–
20 mA or 4–20 mA?
Field O311
Diagnostics and troubleshooting Liquisys M CCM223/253
92 Endress+Hauser
Error Possible cause Tests/remedial action Tools, spare parts
Total load in the current
loop too high (> 500 Ω)
Disconnect output and measure
directly at device
mA meter for 0–20 mA DC
EMC (interference
coupling)
Disconnect both output cables
and measure directly at device
Use shielded cables, ground
shields at both ends, where
necessary route cable in
another cable duct
Current output
table is not
accepted
Value interval too small Select practical intervals
No output signal
for temperature or
pH/mV
Device does not have a
second current output
Check version using nameplate,
if necessary replace the LSCH-
x1 module
LSCH-x2 module, see the
"Spare parts" section
Device with PROFIBUS-PA PA device has no current
output!
Chemoclean
function not
available
No relay module (LSR1-x)
installed or only LSR1-2
available
Install LSR1-4 module.
Chemoclean is enabled using
the release code supplied by the
manufacturer in the
Chemoclean retrofit kit.
LSR1-4 module, see the
"Spare parts" section
Plus Package
functions not
available
Plus Package not enabled
(enable by entering a code
which depends on the
serial number and which is
supplied by E+H when a
Plus Package is ordered)
For Plus Package retrofit:
code is supplied by E+H →
enter this code.
After replacing a defective
LSCH/LSCP module: first
enter device serial number
manually (see nameplate),
then enter the existing code
number.
For a detailed description,
see the "Replacement of
central module" section.
No HART
communication
No HART central module Verify using nameplate: HART =
-xxx5xx and -xxx6xx
Upgrade to LSCH-H1 / -H2
No or incorrect DD (device
description)
For further information, see
BA00208C/07/EN, "HART field
communication with Liquisys
CxM223/253”
HART interface missing
Load too small (must be >
230 Ω)
HART receiver (e.g. FXA
191) not connected via
load but via power supply
Incorrect device address
(addr. = 0 for single
operation, addr. > 0 for
multidrop operation)
Line capacitance too high
Interference on line
Several devices set to same
address
Assign addresses correctly No communication possible
if several devices set to the
same address
No PROFIBUS
communication
No PA/DP central module Verify using the nameplate: PA
= -xxx3xx /DP = xxx4xx
Upgrade to LSCP module,
see the "Spare parts" section
Incorrect device software
version (without
PROFIBUS)
For further information, see
BA00209C/07/EN "PROFIBUS
PA/DP - Field communication
for Liquisys CxM223/253".
Information about
PROFIBUS configuration is
provided in Technical
Information TI00260F,
while detailed information
about instrumentation and
accessories is provided in
Operating Instructions
BA00198F
With Commuwin (CW) II:
CW II version and device
software version
incompatible
No or incorrect DD/DLL
Liquisys M CCM223/253 Diagnostics and troubleshooting
Endress+Hauser 93
Error Possible cause Tests/remedial action Tools, spare parts
Incorrect baud rate setting
for segment coupler in
DPV-1 server
Bus user (master) has
wrong address or address
assigned twice
Bus user (slave) has wrong
address
Bus line not terminated
Line problems (too long,
cross-section too small,
not shielded, shield not
grounded, wires not
twisted)
Bus voltage too low
(Bus voltage typ. 24 V DC
for non-Ex)
The voltage at the device's
PA/DP connector must be at
least 9 V
8.4 Device-specific errors
The following table helps you during the diagnosis and points to any spare parts required.
Depending on the degree of difficulty and the measuring equipment present, diagnosis is
carried out by:
Trained operator personnel
The user's trained electrical technicians
Company responsible for system installation/operation
Endress+Hauser Service
Information on the exact spare part designations and on how to install these parts can be
found in the "Spare parts" section.
Error Possible cause Tests/remedial action Execution, tools, spare
parts
Device cannot be
operated, display
value 9999
Operation locked Press CAL and MINUS keys
simultaneously.
See the "Key functions"
section
Display dark, no
light-emitting
diode active
No line voltage Check whether line voltage is
present
Electrical technician / e.g.
multimeter
Supply voltage
wrong/too low
Compare actual line voltage
and nameplate data
User (data for energy supply
company or multimeter)
Connection faulty Terminal not tightened
Insulation jammed
Wrong terminals used
Electrical technician
Device fuse defective Compare line voltage and the
nameplate data and replace
fuse
Electrical technician/suitable
fuse; see exploded drawing in
the the "Spare parts" section
Power unit defective Replace power unit, note
version
Onsite diagnosis by Endress
+Hauser Service, test module
necessary
Central module defective Replace central module, note
version
Onsite diagnosis by Endress
+Hauser Service, test module
necessary
Field device: ribbon cable
loose or defective
Check ribbon cable, replace if
necessary
See the "Spare parts" section
Diagnostics and troubleshooting Liquisys M CCM223/253
94 Endress+Hauser
Error Possible cause Tests/remedial action Execution, tools, spare
parts
Display dark, light-
emitting diode
active
Central module defective
(module: LSCH/LSCP)
Replace central module, note
version
Onsite diagnosis by Endress
+Hauser Service, test module
necessary
Values appear on
display but:
Display does not
change and / or
Device cannot
be operated
Device or module in
device not correctly
mounted
Panel-mounted device: reinstall
insert.
Field device: remount display
module
Perform with the aid of the
installation drawings in the
the "Spare parts" section
Impermissible operating
system condition
Disconnect line voltage for
approx. 10 seconds
Possibly Possible EMC
problem: if this persists,
check the installation or have
checked by Endress+Hauser
Service
Device gets hot Voltage wrong/too high Compare line voltage and
nameplate data
User, electrical technician
Power unit defective Replace power unit Diagnosis only by Endress
+Hauser Service
Cl/ClO
2
measured
value and/or
temperature
measured value
incorrect
Transmitter module
defective (module:
MKIC), please first carry
out tests and take
measures as per the
"Process-specific errors"
section
Measuring input test:
Chlorine input open = display
0.00 mg/l
10 kΩ resistance at terminals
11 + 12 = display 25 °C
If test negative: replace
module (note version)
Perform with the aid of the
exploded drawings in the
"Spare parts" section.
Current output,
incorrect current
value
Incorrect adjustment Check with integrated current
simulation, connect mA meter
directly to current output.
If simulation value incorrect:
adjustment in factory or new
LSCH module required.
If simulation value correct:
check current loop for load
and shunts.
Load too large
Shunt / short to ground
in current loop
Incorrect mode of
operation
Check whether 0–20 mA or 4–
20 mA is selected.
No current output
signal
Current output stage
defective (only for LSCH
module; LSCP has no
current output)
Check with integrated current
simulation, connect mA meter
directly to current output
If test negative:
Replace central module (note
version)
Additional relays
not working
Field device: ribbon cable
loose or defective
Check ribbon cable seating,
replace cable if required.
See the "Spare parts" section
Only 2 additional
relays can be
triggered
LSR1-2 relay module
with 2 relays is installed
Upgrade to LSR1-4 with 4
relays.
User or Endress+Hauser
Service
Additional
functions (Plus
Package) missing
No or incorrect release
code used
If retrofitting: check whether
the correct serial number was
quoted when ordering the Plus
Package.
Handled by Endress+Hauser
Sales
Incorrect device serial
number saved in LSCH/
LSCP module
Check whether serial number
on the nameplate matches SNR
in LSCH/ LSCP (field S 8).
The serial number of the
device is definitive for the
Plus Package.
Additional
functions (Plus
Package and/or
Chemoclean)
missing after
LSCH/LSCP
module
replacement
Replacement modules
LSCH or LSCP have the
device serial number
0000 when they leave
the factory. The Plus
Package or Chemoclean
are not enabled on
leaving the factory.
In the case of LSCH/LSCP with
SNR 0000, a device serial
number can be entered once in
fields E115 to E117.
Then enter the release codes
for the Plus Package and/or
Chemoclean if necessary.
For a detailed description,
see the "Replacement of
central module" section.
Liquisys M CCM223/253 Maintenance
Endress+Hauser 95
Error Possible cause Tests/remedial action Execution, tools, spare
parts
No HART or
PROFIBUS PA/DP
interface function
Incorrect central module HART: LSCH-H1 or H2 module,
PROFIBUS-PA: LSCP-PA
module,
PROFIBUS-DP: LSCP-DP
module,
see field E112.
Replace central module;
User or Endress+Hauser
Service.
Wrong software SW version, see field E111.
Bus problem Remove some devices and
repeat the test.
Contact Endress+Hauser
Service.
9 Maintenance
L
WARNING
Process pressure and temperature, contamination, electrical voltage
Risk of serious or fatal injury
If the sensor has to be removed during maintenance work, avoid hazards posed by
pressure, temperature and contamination.
Make sure the device is de-energized before you open it.
Power can be supplied to switching contacts from separate circuits. De-energize these
circuits before working on the terminals.
Take all the necessary precautions in time to ensure the operational safety and reliability
of the entire measuring point.
The maintenance of the measuring point comprises:
Calibration
Cleaning the controller, assembly and sensor
Checking the cables and connections
When performing any work on the device, bear in mind any potential impact this may
have on the process control system or on the process itself.
NOTICE
Electrostatic discharge (ESD)
Risk of damaging the electronic components
Take personal protective measures to avoid ESD, such as discharging beforehand at PE
or permanent grounding with a wrist strap.
For your own safety, only use genuine spare parts. With genuine parts, the function,
accuracy and reliability are also ensured after maintenance work.
9.1 Maintenance of the entire measuring point
9.1.1 Cleaning the transmitter
Clean the front of the housing using commercially available cleaning agents only.
The front of the housing is resistant to the following in accordance with DIN 42 115:
Ethanol (for a short time)
Diluted acids (max. 2% HCl)
Diluted alkaline solutions (max. 3% NaOH)
Soap-based household cleaning agents
When performing any work on the device, bear in mind any potential impact this may
have on the process control system or on the process itself.
Maintenance Liquisys M CCM223/253
96 Endress+Hauser
NOTICE
Prohibited cleaning agents
Damage to the housing surface or housing seal
Never use concentrated mineral acids or alkaline solutions for cleaning.
Never use organic cleaners such as benzyl alcohol, methanol, methylene chloride,
xylene or concentrated glycerol cleaner.
Never use high-pressure steam for cleaning purposes.
9.1.2 Cleaning the pH/mV sensors (EP version)
L
CAUTION
Cleaning not switched off during calibration or maintenance activities
Risk of injury due to medium or cleaning agent
If a cleaning system is connected, switch if off before removing a sensor from the
medium.
If you wish to check the cleaning function and have therefore not switched off the
cleaning system, please wear protective clothing, goggles and gloves or take other
appropriate measures.
L
CAUTION
Risk of injury from cleaning agents
When using the following cleaning agents, make sure to protect your hands, eyes and
clothing.
Please clean contamination on the glass electrodes as follows:
Oily and greasy films:
Clean with hot water or temperature-controller detergent (grease remover, e.g. alcohol,
acetone, possibly dishwashing detergent).
Lime and metal hydroxide buildup:
Dissolve buildup with diluted hydrochloric acid (3 %) and then rinse thoroughly with
plenty of clear water.
Sulfidic buildup (from flue gas desulfurization or sewage treatment plants):
Use a mixture of hydrochloric acid (3 %) and thiocarbamide (commercially available) and
then rinse thoroughly with plenty of clear water.
Buildup containing proteins (e.g. food industry):
Use a mixture of hydrochloric acid (0.5 %) and pepsin (commercially available) and then
rinse thoroughly with plenty of clear water.
Fibers, suspended substances:
Pressurized water, surface-active agents if necessary
Light biological buildup:
Pressurized water
ORP electrodes:
Carefully clean the metal pins or surfaces mechanically.
After mechanical cleaning, the ORP sensor can require several hours conditioning
time. For this reason, check the calibration after one day.
ISFET sensors
Never use acetone to clean ISFET sensors as this could damage the material.
After being cleaned with compressed air, ISFET sensors require approx. 5 to 8 minutes
until the closed-control loop is re-established and the measured value has adjusted to
the real value.
Clogged membranes can be cleaned mechanically under certain circumstances (does not
apply to ISFET sensors, Teflon membranes and open ring junction electrodes):
Use a small warding file.
Only file in one direction.
Liquisys M CCM223/253 Maintenance
Endress+Hauser 97
Air bubbles in the electrode:
Air bubbles can indicate incorrect mounting. For this reason check the orientation.
The range 15° to 165° to the horizontal is allowed (ISFET sensors are the exception).
Not permitted: horizontal installation or installation with the plug-in head pointing
downwards.
> 15°
> 15°
A0027183
 44 Permitted angle of installation for glass electrodes
Check for reference system reduction
The inner reference lead of the reference system (Ag/AgCl) of a combination electrode or
a separate reference electrode is usually brownish and matt. A silver-colored reference
system is reduced and therefore defective. This is caused by a current flowing through the
reference element.
Possible causes for the current flow:
Incorrect measuring device operating mode selected (PML pin connected, but operating
mode asymmetrical ("without PML"). See also the function description for "Selecting the
connection type".
Shunt in measuring cable (e.g. due to moisture) between reference line and grounded
shield or PM line.
Measuring device defective (shunt in reference input or entire input amplifier
downstream of PE).
9.1.3 Maintenance of chlorine sensors
Please refer to the Operating Instructions for your sensor for sensor maintenance and
troubleshooting:
CCS120 BA00388C/07/EN
CCS140/141 BA00058C/07/EN
CCS240/241 BA00114C/07/EN
963 BA00039C/07/EN
The Operating Instructions contain detailed information including:
Sensor design and function
Mounting and installation
Electrical connection
Commissioning and calibration
Calculation examples and tables for verification of measured values
Maintenance, regeneration, cleaning
Troubleshooting table
Accessories and spare parts
Technical data and ordering information
9.1.4 Assembly
Refer to the assembly operating manual for information on servicing and troubleshooting
the assembly. The assembly operating manual describes the procedure for mounting and
disassembling the assembly, replacing the sensors and seals, and contains information on
the material resistance properties, as well as on spare parts and accessories.
Maintenance Liquisys M CCM223/253
98 Endress+Hauser
9.1.5 Maintenance of pH connecting cables and junction boxes (EP
version)
Check the cables and connections for moisture. Moisture is indicated by a sensor slope that
is too small. If nothing more can be displayed or if the display is fixed at pH 7, please check
the following components:
Sensor head
Sensor plug
Junction box, if fitted
Extension cable
NOTICE
Incorrect measurements caused by moisture in the measuring cable
If there is moisture in the measuring cable, the cable must be replaced!
A shunt in the cable of > 20 MΩ cannot be measured with normal multimeters but is
damaging for the pH measurement. Connect a pH simulator instead of the sensor. The
value that is displayed on the transmitter must match the value set at the simulator. The
value can differ at the second decimal place at the very maximum.
If you do not have a pH simulator, you can test the cable with a commercially available
megohmmeter. Please note the following when performing the test:
Make sure to disconnect the pH measuring cable from the sensor and device!
If you are using a junction box, you should check the infeed and outfeed measuring cable
separately.
Check the cable with 1000 V DC (at least with 500 V DC) testing voltage.
If the cable is intact, the insulation resistance is > 100 GΩ.
If the cable is defective (moist), there is flashover.
The cable must be replaced.
You can clean (desalinate) the sensor head and junction box with de-ionized water
and dry them with a hot air dryer.
9.2 Test and simulation
9.2.1 Chlorine sensors
Chlorine sensors work according to the amperometric principle and supply very small
direct currents as the measuring signal.
A chlorine sensor can be simulated by a DC source. Due to the small currents, however, the
simulation is highly sensitive. Use shielded cables and ground the simulator. Typical slope
values are provided in the table below:
Sensor Typical slope value
CCS120 Approx. 115 nA per mg Cl/l
CCS140 Approx. 25 nA per mg Cl/l
CCS141 Approx. 80 nA per mg Cl/l
CCS240 Approx. 100 nA per mg ClO
2
/l
CCS241 Approx. 350 nA per mg ClO
2
/l
963 Approx. 20 μA per mg Cl/l
Liquisys M CCM223/253 Maintenance
Endress+Hauser 99
9.2.2 Temperature measurement
The transmitter uses the NTC sensor of the chlorine sensor to measure the temperature.
Due to the relatively high sensor resistance, a two-wire connection is sufficient.
Simulation can be performed with a normal decade resistor. The table below contains
some simulation values:
Temperature NTC simulation value
0 °C (32 °F) 29.490 kΩ
10 ° C (50 °F) 18.787 kΩ
20 °C (68 °F) 12.268 kΩ
25 °C (77 °F) 10.000 kΩ
30 °C (86 °F) 8.197 kΩ
40 °C (104 °F) 5.594 kΩ
9.2.3 pH/ORP measurement
Simulation is performed with a pH/mV simulator or an mV voltage source.
In the case of the CCM223/253, the pH or mV must always be measured
symmetrically. For this reason, each simulation requires potential matching with the
simulator. Connect the reference signal of the simulator (normal shield of the pH
coaxial measuring line) to the PA/PM terminal of the transmitter.
Zero point rapid test
In the case of the panel-mounted device, connect the BNC inner conductor to the BNC
receptacle and the PM terminal.
In the case of the field device, connect the pH terminal, the Ref terminal and the PM
terminal.
For pH the reading must be approx. 7, and for ORP approx. 0 mV.
Test with DC supply point
pH value Simulation
2 295 mV
4 177 mV
7 0 mV
9 -118 mV
12 -295 mV
9.2.4 Flow monitoring
Flow is monitored by an inductive proximity switch (INS) in the CCA250 assembly. This
switch is powered by 15 V from the auxiliary voltage output of the transmitter.
Function of the INS
Flow INS INS output
Yes damped low impedance
No not damped high-impedance
Test or emergency mode
Maintenance Liquisys M CCM223/253
100 Endress+Hauser
If you connect terminal 93 to terminal 85 and terminal 94 to terminal 86, this simulates
an active proximity switch and thus a correct flow.
Do not run the measuring system continuously in this state. Reestablish flow
monitoring as soon as possible!
Liquisys M CCM223/253 Repair
Endress+Hauser 101
10 Repair
10.1 Spare parts
Please order spare parts from your local Sales Office. For this purpose, use the order
numbers listed in the "Spare part kits" section.
For safety, you should always provide the following additional data when ordering spare
parts:
Device order code
Serial number
Software version, if possible
You can take the order code and serial number from the nameplate.
The software version is provided in the device software provided that the device processor
system is still working.
For more detailed information on spare parts kits, please refer to the "Spare Part Finding
Tool" on the Internet:
www.endress.com/spareparts_consumables
10.2 Disassembling the panel-mounted device
Please note the effects on the process if the device is taken out of service!
See the exploded drawing for the item numbers.
1. Disconnect the terminal block (item 150 to 180) from the rear of the device to de-
energize the device.
2. Press in the latches of the end frame (item 340) and remove the frame from the rear.
3. Release the special screw (item 400) by turning it counter-clockwise.
4. Remove the entire electronics block from the housing. The modules are only
mechanically connected and can be easily separated:
5. Simply remove the processor/display module towards the front.
6. Pull out the brackets of the rear plate (item 320) slightly.
7. Now you can remove the side modules.
8. Remove the Cl transmitter (item 110/120) as follows:
9. Using a fine wire cutter, nip off the heads of the synthetic distance holders.
10. Then remove the module from above.
Assembly is the reverse of the disassembly sequence. Tighten the special screw finger-
tight without using a tool.
Repair Liquisys M CCM223/253
102 Endress+Hauser
150 -170
340
400
210
C
200
110/120
10/20
50 - 100
130
320
310
180
30 - 45
10
15
230 V
115 V
100 V
A
B
A0001912
 45 Exploded drawing of panel-mounted device
Liquisys M CCM223/253 Repair
Endress+Hauser 103
The exploded drawing contains the components and spare parts of the panel-mounted
device. You can take the spare parts and the corresponding order number from the
following section using the item numbers.
Item Kit description Name Function/contents Order no.
10 Power unit (main
module)
LSGA 100/115/230 V AC 51500317
15 Jumper Part of power unit, item 10
20 Power unit (main
module)
LSGD 24 V AC + DC 51500318
30 Relay module LSR1-2 2 relays 51500320
35 Relay module LSR2-2i 2 relays + 4-20 mA current input 51504304
35 Kit for Cxm2x3 relay
module
PROFIBUS DP
LSR2-DP Relay module + 2 relays
Curr. input + DP terminals
Hardware version 2.10 and higher
71134732
40 Relay module LSR1-4 4 relays 51500321
45 Relay module LSR2-4i 4 relays + 4-20 mA current input 51504305
50 Central module LSCH-S1 1 current output 51502467
50 Kit for CCM2x3 central
module
PROFIBUS DP
LSCP PROFIBUS DP central module
Relay module + 2 relays
Curr. input + DP terminals
Hardware version 2.10 and higher
71134731
60 Central module LSCH-S2 2 current outputs 51502468
70 Central module LSCH-H1 1 current output + HART 51502497
80 Central module LSCH-H2 2 current outputs + HART 51502496
90 Central module LSCP-PA PROFIBUS PA/no current output 51502495
100 Central module LSCP-DP PROFIBUS DP/no current output 51502498
110 Cl transmitter MKC1 Input Cl and temperature 51502466
120 Cl/pH transmitter MKC1 Input Cl, pH/mV, temperature 51502465
130, 400 Housing module Housing with front membrane, sensory
tappets, seal, special screw, tensioning
dogs, connection plates and nameplates
51501075
150 Complete terminal strip
set
Standard + HART
Terminal strip set, inputs/outputs,
power supply, alarm relay
51502463
160 Complete terminal strip
set
PROFIBUS-PA
Terminal strip set, inputs/outputs,
power supply, alarm relay
51502464
170 Complete terminal strip
set
PROFIBUS-DP
Terminal strip set, inputs/outputs,
power supply, alarm relay
51502490
180 Terminal strip Terminal strip for relay modules 51501078
200 pH input socket Socket with screen plate 51501070
210 BNC connector BNC easy solder-free, angled 50074961
310, 320,
340, 400
Housing mechanical
parts
Rear plate, side panel, end frame, special
screw
51501076
340 End frame
PROFIBUS-DP
Rear frame for PROFIBUS DP, with D-
submin plug connector
51502513
A Fuse Part of power unit, item 10
B Choice of line voltage Position of jumper on power unit, item 10
depending on line voltage
C End frame latches Part of the end frame
Repair Liquisys M CCM223/253
104 Endress+Hauser
10.3 Disassembling the field device
Please note the effects on the process if the device is taken out of service!
See the exploded drawing for the item numbers.
You require the following tools to disassemble the field device:
Standard set of screwdrivers
Torx screwdriver, size TX 20
Proceed as follows to disassemble the field device:
1. Open and remove the cover of the connection compartment (item 420).
2. Disconnect the supply terminal (item 270)) to de-energize the device.
3. Open the display cover (item 410) and release the ribbon cables (item 250) on the
central module side (item 50 to 100) .
4. To remove the central module (item 50) release the screw in the display cover (item
450 b).
5. Proceed as follows to remove the electronics box (item 230) :
6. Turn the screws in the housing base (item 450 a) by two revolutions to release them.
7. Then push the entire box backwards and remove it from above while making sure
that the module locks do not open.
8. Release the ribbon cables (item 250) .
9. Bend the module locks out and remove the modules.
10. To remove the docking module (item 240) remove the screws in the housing base
(item 450 c) and remove the entire assembly from above.
11. To remove the CI transmitter (item 110/120) on devices with a pH/mV input, bend
the shielding plate up.
12. Disconnect the connected strand (pH input, strand comes from the BNC connection
jack) and nip off the heads of the synthetic distance sleeves using a fine wire cutter.
13. Then remove the module from above.
To assemble, carefully push the modules into the guide rails of the electronics box and let
them engage in the side box noses.
It is not possible to mount the modules incorrectly. Modules inserted in the electronics
box incorrectly are not operable since the ribbon cables cannot be connected.
Make sure the cover seals are intact to guarantee IP 65 ingress protection.
Liquisys M CCM223/253 Repair
Endress+Hauser 105
A
B
C
D
370
50 - 100
460b
410
420
460a
110/120
250
280
10/20
30 - 45
240
270
480
400
430
230
230 V
115 V
100 V
10
15
450a
450b
450c
A0001915
 46 Field device exploded drawing
Repair Liquisys M CCM223/253
106 Endress+Hauser
The exploded drawing contains the components and spare parts of the field device. You
can take the spare parts and the corresponding order number from the following section
using the item numbers.
Item Kit description Name Function/contents Order no.
10 Power unit (main module) LSGA 100/115/230 V AC 51500317
15 Jumper Part of power unit, item 10
20 Power unit (main module) LSGD 24 V AC + DC 51500318
30 Relay module LSR1-2 2 relays 51500320
35 Relay module LSR2-2i 2 relays + 4-20 mA current input 51504304
35 Kit for Cxm2x3 relay
module
PROFIBUS DP
LSR2-DP Relay module + 2 relays
Curr. input + DP terminals
Hardware version 2.10 and higher
71134732
40 Relay module LSR1-4 4 relays 51500321
45 Relay module LSR2-4i 4 relays + 4-20 mA current input 51504305
50 Central module LSCH-S1 1 current output 51502467
50 Kit for CCM2x3 central
module
PROFIBUS DP
LSCP PROFIBUS DP central module
Relay module + 2 relays
Curr. input + DP terminals
Hardware version 2.10 and higher
71134731
60 Central module LSCH-S2 2 current outputs 51502468
70 Central module LSCH-H1 1 current output + HART 51502497
80 Central module LSCH-H2 2 current outputs + HART 51502496
90 Central module LSCP-PA PROFIBUS PA/no current output 51502495
100 Central module LSCP-DP PROFIBUS DP/no current output 51502498
110 Cl transmitter MKC1 Input Cl and temperature 51502466
120 Cl/pH transmitter MKC1 Input Cl, pH/mV, temperature 51502465
230, 240 Inner housing fittings Docking module, empty electronics box,
small parts
51501073
250 Ribbon cable lines 2 ribbon cable lines 51501074
270 Terminal strip Terminal strip for connection to power
supply
51501079
280 pH terminal pH terminal with shielding plate 51501071
370, 410,
420, 430,
460
Housing cover Display cover, connection compartment
cover, front membrane, hinges, cover
screws, small parts
51501068
400, 480 Housing base Base, threaded joints 51501072
310, 320,
340, 400
Housing mechanical parts Rear plate, side panel, end frame, special
screw
51501076
A Electronics box with relay
module LSR1-x (bottom)
and power unit LSGA/
LSGD (top)
B Fuse also accessible if
electronics box installed
C Fuse Part of power unit, item 10
D Choice of line voltage Position of jumper on power unit, item
10 depending on line voltage
Liquisys M CCM223/253 Repair
Endress+Hauser 107
10.4 Replacing the central module
Generally, when a central module has been replaced, all data which can be changed
are set to the factory setting.
If possible, note the customized settings of the device, such as:
Calibration data
Current assignment, main parameter and temperature
Relay function selections
Limit value/controller settings
Cleaning settings
Monitoring functions
Interface parameters
Proceed as described below if a central module is replaced:
1. Disassemble the device as explained in the "Dismantling the panel-mounted
instrument" or "Dismantling the field instrument" section.
2. Use the part number on the central module to check whether the new module has
the same part number as the previous module.
3. Reassemble the device with the new module.
4. Put the device back into operation and check the basic functions (e.g. measured value
and temperature display, operation via keyboard).
5. Read the serial number (“ser-no.”) off the nameplate of the device (e.g.
6A345605G00) and enter this number in fields E115 (1st digit = year, one-digit (6
in the example)), E116 (2nd digit: month, one-digit (A in the example)), E117 (digits
3-6 cons. number, four-digit (3456 in the example)).
In the field E118, the complete number is displayed again so you can check it is
correct.
You can only enter the serial number for new modules with the serial number 0000.
This can only be done once! For this reason, make sure the number entered is correct
before you press ENTER to confirm!
If an incorrect code is entered, the additional functions are not enabled. An incorrect
serial number can only be corrected at the factory!
1. Press ENTER to confirm the serial number or cancel the entry to enter the number
again.
2. If available, enter the release codes for the Plus Package and/or Chemoclean in the
"Service" menu.
3. Check the Plus Package release (e.g. by opening the function group CHECK / Code P)
or the Chemoclean function.
4. Make the customized device settings again.
10.5 Return
The product must be returned if repairs or a factory calibration are required, or if the
wrong product was ordered or delivered. As an ISO-certified company and also due to legal
regulations, Endress+Hauser is obliged to follow certain procedures when handling any
returned products that have been in contact with medium.
To ensure swift, safe and professional device returns, please read the return procedures
and conditions at www.endress.com/support/return-material.
Repair Liquisys M CCM223/253
108 Endress+Hauser
10.6 Disposal
The device contains electronic components and must therefore be disposed of in
accordance with regulations on the disposal of electronic waste.
Observe the local regulations.
Liquisys M CCM223/253 Accessories
Endress+Hauser 109
11 Accessories
11.1 Sensors
CCS120
Amperometric sensor for total chlorine
Measuring range 0.1 to 10 mg/l
Product Configurator on the product page: www.endress.com/ccs120
Technical Information TI00388C
CCS140
Membrane-covered amperometric sensor for free chlorine
Measuring range 0.05 to 20 mg/l
Product Configurator on the product page: www.endress.com/ccs140
Technical Information TI00058C
CCS141
Membrane-covered amperometric trace sensor for free chlorine
Measuring range 0.01 to 5 mg/l
Product Configurator on the product page: www.endress.com/ccs141
Technical Information TI00058C
CCS240
Membrane-covered amperometric sensor for chlorine dioxide
Measuring range 0.05 to 20 mg/l
Product Configurator on the product page: www.endress.com/ccs240
Technical Information TI00114C
CCS241
Membrane-covered amperometric trace sensor for chlorine dioxide
Measuring range 0.01 to 5 mg/l
Product Configurator on the product page: www.endress.com/ccs241
Technical Information TI00114C
11.2 Connection accessories
Measuring cable CYK71
Unterminated cable for connecting analog sensors and for extending sensor cables
Sold by the meter, order numbers:
Non-Ex version, black: 50085333
Ex-version, blue: 50085673
CPK1
For pH/ORP electrodes with GSA plug-in head
Ordering information is available from your sales office or at www.endress.com.
CPK9
Terminated measuring cable for connecting analog sensors with TOP68 plug-in head
Selection in accordance with product structure
For more information and to order, please contact your sales office.
Accessories Liquisys M CCM223/253
110 Endress+Hauser
MK extension cable
Twin-core signal cable with additional shielding and PVC insulation
Particularly for the transmission of output signals of transmitters or input signals of
controllers and for temperature measurement.
Order number: 50000662
VBC junction box
For cable extension (for chlorine measuring systems)
Dimensions (B x D x H): 125 x 80 x 54 mm (4.92 x 3.15 x 2.13 ")
10 terminal strips
Cable entries: 7 x Pg 7, 2 x Pg 11
Material: aluminum
Degree of protection: IP 65 (i NEMA 4x)
Order No. 50005181
VBM
Junction box for cable extension
10 terminal strips
Cable entries: 2 x Pg 13.5 or 2 x NPT ½"
Material: aluminum
Degree of protection: IP 65
Order numbers
Cable entries Pg 13.5 : 50003987
Cable entries NPT ½": 51500177
11.3 Installation accessories
CYY101
Weather protection cover for field devices
Absolutely essential for field installation
Material: stainless steel 1.4301 (AISI 304)
Order No. CYY101-A
320 (12.6)
270 (10.6)
300 (11.8)
A0024627
 47 Dimensions in mm (inch)
Flexdip CYH112
Modular holder system for sensors and assemblies in open basins, channels and tanks
For Flexdip CYA112 water and wastewater assemblies
Can be affixed anywhere: on the ground, on the capstone, on the wall or directly onto
railings.
Stainless steel version
Product Configurator on the product page: www.endress.com/cyh112
Technical Information TI00430C
Liquisys M CCM223/253 Accessories
Endress+Hauser 111
Post mounting kit
For securing the field housing to horizontal and vertical posts and pipes
Material: stainless steel 1.4301 (AISI 304)
Order No. 50086842
70 (2.76)
90 (3.54)
Ø 6 (0.24)
Ø 8 (0.31)
70 (2.76)
90 (3.54)
M6
60 (2.36)
90 (3.54)
70 (2.76)
Ø 8 (0.31)
30 (1.18)
Ø max. 60 (2.36)
A0024660
 48 Dimensions in mm (inch)
11.4 Software and hardware add-ons
The add-ons can only be ordered by quoting the serial number of the device in question.
Plus Package
Order No. 51502242
Chemoclean function (requires four-relay card)
Order No. 51502871
Two-relay card
Order No. 51500320
Four-relay card
Order No. 51500321
Two-relay card with current input
Order No. 51504304
Four-relay card with current input
Order No. 51504305
pH package for EK version
Order No. 51502460
pH package for ES version
Order No. 51503526
11.5 Metering system
Compact measuring station CCE10/CCE11
Fully assembled and wired panel for one or three transmitters, with CCA250-A1 flow
assembly
Product Configurator on the product page: www.endress.com/cce10 or
www.endress.com/cce11
Technical Information TI00440C
Accessories Liquisys M CCM223/253
112 Endress+Hauser
11.6 Calibration accessories
Photometer PF-3
Compact hand-held photometer for determining free available chlorine
Color-coded reagent bottles with clear dosing instructions
Order No.: 71257946
Liquisys M CCM223/253 Technical data
Endress+Hauser 113
12 Technical data
12.1 Input
Measured variables Total chlorine
Free available chlorine
Chlorine dioxide
Temperature
pH value or ORP (optional)
Cl
2
/ClO
2
signal input CCS120/140/141/240/241: 0 to 5000 nA
Sensor 963: -100 to 500 µA
Temperature measurement
Temperature sensor for
CCS120/140/141/240/241:
NTC, 10 kΩ at 25 °C (77 °F)
Display range: 0 to 50 °C (32 to 122 °F)
pH and ORP measurement pH measuring range: pH 3.5 to 9.5
ORP measuring range: 0 to 1500 mV
Zero point adjustment: ±100 mV
Slope adjustment 38 to 65 mV/pH
Binary inputs Voltage 10 to 50 V
Current consumption Max. 10 mA
Current input 4 to 20 mA, galvanically isolated
Load: 260 Ω for 20 mA (voltage drop 5.2 V)
12.2 Output
Output signal
HART
Signal encoding Frequency Shift Keying (FSK) + 0.5 mA via current output signal
Data transmission rate 1200 baud
Galvanic isolation Yes
PROFIBUS PA
Signal encoding Manchester Bus Powered (MBP)
Data transmission rate 31.25 kBit/s, voltage mode
Galvanic isolation Yes (IO modules)
Technical data Liquisys M CCM223/253
114 Endress+Hauser
PROFIBUS DP
Signal encoding RS485
Data transmission rate 9.6 kBd, 19.2 kBd, 93.75 kBd, 187.5 kBd, 500 kBd, 1.5 MBd
Galvanic isolation Yes (IO modules)
Signal on alarm 2.4 or 22 mA in the event of an error
Load Max. 500 Ω
Transmission range Cl
2
/ClO
2
CCS120 0 to 10 mg/l
CCS140/240 0 to 20 mg/l
CCS141/241 and 963 0 to 5 mg/l
Temperature 0 to 50 °C (32 to 120 °F)
pH 4 to 9
ORP 0 to 1500 mV
Signal resolution Max. 700 digits/mA
Separation voltage Max. 350 V
RMS
/ 500 V DC
Auxiliary voltage output
Output voltage 15 V ± 0.6 V
Output current Max. 10 mA
Contact outputs Switching current with ohmic load (cos φ = 1) Max. 2 A
Switching current with inductive load (cos φ =
0.4)
Max. 2 A
Switching voltage Max. 250 V AC, 30 V DC
Switching power with ohmic load (cos φ = 1) Max. 500 VA AC, 60 W DC
Switching power with inductive load (cos φ =
0.4)
Max. 500 VA AC, 60 W DC
Limit contactors
Pickup/dropout delay 0 to 2000 s
Controller
Function (configurable) Pulse length/pulse frequency controller,
continuous controller
Three-point step controller for Cl
2
/ClO
2
Controller behavior P, PI, PD, PID, basic load dosing
Control gain K
p
0.01 to 20.00
Integral action time T
n
0.0 to 999.9 min
Derivative action time T
v
0.0 to 999.9 min
Period length for pulse length controller 0.5 to 999.9 s
Frequency for pulse frequency controller 60 to 180 min
-1
Basic load 0 to 40 % of max. actuating variable
Motor run time for three-point step controller 10 to 999 s
Neutral zone for three-point step controller 0 to 40 %
Liquisys M CCM223/253 Technical data
Endress+Hauser 115
Alarm Function (switchable) Latching/momentary contact
Alarm threshold adjustment range Cl
2
/ClO
2
/pH/ORP/temperature: entire
range
Alarm delay 0 to 2000 s
Monitoring time for lower limit violation 0 to 2000 min
Monitoring time for upper limit violation 0 to 2000 min
Protocol-specific data
HART
Manufacturer ID 11
h
Device type 0094
h
Transmitter-specific revision 0001
h
HART version 5.0
Device description files (DD) www.endress.com/hart
HART load (communication resistor) 250 Ω
Device variables None (only dynamic variables PV and SV)
Supported features -
PROFIBUS PA
Manufacturer ID 11
h
Device type 1518
h
Device revision 0001
h
Profile version 2.0
GSD files www.endress.com/profibus
GSD version
Output values Primary value, temperature
Input variables PCS display value
Supported features Device lock: The device can be locked
using the hardware or software.
PROFIBUS DP
Manufacturer ID 11
h
Device type 151E
h
Profile version 2.0
GSD files www.endress.com/profibus
GSD version
Output values Primary value, temperature
Input variables PCS display value
Supported features Device lock: The device can be locked
using the hardware or software.
Technical data Liquisys M CCM223/253
116 Endress+Hauser
12.3 Power supply
Supply voltage Depending on order version:
100/115/230 V AC +10/-15 %, 48 to 62 Hz
24 V AC/DC +20/-15 %
Power supply via fieldbus
HART
Supply voltage Not applicable, active current outputs
Reverse polarity protection Not applicable, active current outputs
PROFIBUS PA
Supply voltage 9 V to 32 V, max. 35 V
Sensitivity to reverse polarity No
FISCO/FNICO compliant according to IEC
60079-27
No
PROFIBUS DP
Supply voltage 9 V to 32 V, max. 35 V
Sensitivity to reverse polarity Not applicable
FISCO/FNICO compliant according to IEC
60079-27
No
Power consumption Max. 7.5 VA
Mains fuse Fine-wire fuse, semi-delay 250 V/3.15 A
Circuit breaker
NOTICE
The device does not have a power switch
The customer must provide a protected circuit breaker in the vicinity of the device.
The circuit breaker must be a switch or power switch, and you must label it as the
circuit breaker for the device.
At the supply point, the power supply for the 24 V versions must be isolated from
dangerous live cables by double or reinforced insulation.
Cable specification Cable length (CCS140/141/240/241) Max. 30 m (98 ft) with CMK cable
Cable length (chlorine sensor 963) Max. 30 m (98 ft) with CMK cable
Cable length (CCS120) Max. 15 m (49 ft) with CPK9 cable
Cable length (pH/ORP) Max. 50 m (160 ft) with cable CYK71
Overvoltage protection According to EN 61000-4-5
Liquisys M CCM223/253 Technical data
Endress+Hauser 117
12.4 Performance characteristics
Reference operating
conditions
Reference temperature: 25 ˚C (77 ˚F)
Measured value resolution
CCS120/140/240 and 963
CCS141/241
0.01 mg/l
0.001 mg/l
pH value 0.01 pH
ORP 1 mV
Temperature 0.1 °C
Maximum measured error Display(pH, T = const.)
CCS140/141/240/241
CCS120 and 963
Max. 0.5 % of measured value ± 4 digits
Max. 1 % of measured value ±4 digits
0.03 pH
3 mV
Temperature ±0.3 K
Signal output
CCS140/141/240/241/
CCS120/963
pH
Max. 0.75 % of measuring range
ORP Max. 1.25 % of current output range
Max. 1.25 % of current output range
Temperature Max. 1.25 % of measuring range
Measured errors in accordance with DIN IEC 746 Part 1, at rated operating conditions
Repeatability Max. 0.2 % of measuring range
12.5 Environment
Ambient temperature
range
-10 to +55 °C (+10 to +130 °F)
Storage temperature –25 to +65 °C (-10 to +150 °F)
Electromagnetic
compatibility
Interference emission and interference immunity as per EN 61326-1:2006, EN
61326-2-3:2006
Degree of protection Field device IP 65 / integrity according to NEMA 4X
Panel-mounted device IP 54 (front), IP 30 (housing)
Electrical safety As per EN/IEC 61010-1:2010, overvoltage category II for installations up to
2000 m (6500 ft) above MSL
CSA Device versions with CSA General Purpose approval are certified for indoor use.
Technical data Liquisys M CCM223/253
118 Endress+Hauser
Relative humidity 10 to 95%, not condensing
Degree of contamination The product is suitable for pollution degree 2.
12.6 Mechanical construction
Dimensions
Panel-mounted device L x B x D: 96 x 96 x 145 mm (3.78" x 3.78" x 5.71")
Installation depth: approx. 165 mm (6.50 ")
Field device L x B x D: 247 x 170 x 115 mm (9.72" x 6.69" x 4.53")
Weight Panel-mounted device Max. 0.7 kg (1.54 lbs.)
Field device Max. 2.3 kg (5.07 lbs.)
Materials Panel-mounted device housing Polycarbonate
Field housing ABS PC FR
Front membrane Polyester, UV-resistant
Terminals
Cable cross-section Max. 2.5 mm
2
(14 AWG)
Liquisys M CCM223/253 Appendix
Endress+Hauser 119
13 Appendix
Appendix Liquisys M CCM223/253
120 Endress+Hauser
C
A6A2
A1
A3
A4 A5
A
B
Z
O332
B5
O333
B2
O3(3)
B3
O331
B4
O3(2)
O321
O O1 O2 O3(1) O311 O312 O313
C15C12 C13 C14C11
F2F1F F5F3 F4 F6
Z5Z1 Z2 Z3 Z4
Z6
C15
C14 C15
Only display switchover!
CURRENT INPUT
SETUP 2
SETUP 1
CURRENT OUTPUT
1st error displayed
(if present)
Other errors are
displayed
(up to max. 10 errors)
Meas. value display
Current input in %
Meas. value display
Current input in mA
Controller switch-off
by sample stream
INSOff;
Select display unit
; ppm; ppbmg/l
Cont. switch-off
by current input
InputOff;
Select current range
020 mA4–20 mA;
Enter 0/4 mA value
0 ... 20 (5) mg/l
0 ... 50 °C
0.00;
0 °C;
Enter 20 mA value
0 ... 20 (5) mg/l
0 ... 50 °C
2.0 (0.5);
50 °C;
lin = linear
PH compensation
ManuOff;
Sw.-off direction
for current input
HighLow;
Select sensor
141; 240; 241;
963; 120
140;
Select current output
Output2Output1;
Enter
DPD value
Value of last cal.
Delay for controller
switch-off sam. stream
0 ... 2000 s0 s
Delay for cont.
switch-off curr. input
0 ... 2000 s0 s
Tab = Table
sim = Simulation
Manual
pH compensation
pH 4.00 ... 9.00
last comp. value
Delay for contr.
swi.-on sam. stream
0 ... 2000 s0 s
Delay for cont.
sw.-on current input
0 ... 2000 s0 s
Enter simulation
0 ... 22.0 mA
val.
current value
Select table
options
editread
Enter no. of
table pairs
1 ... 101
Select
table pairs
1 ... no. Table pair
asign
1
Enter correct
process temperature
0 ... 50 °C
current meas. value
Select
digital input 1
Clean trig.ext.Hold
Sw.-off limit value
for current input
0 ... 100%50%
Enter temperature
difference (offset)
5.0 ... + 5.0 °C
current offset
MEAS. VALUE
DISPLAY
with
TEMPERATURE
READING
in °C
Zero calibration
(only if A1 = 120 or 963)
yesno;
Calibration status
is displayed
Exxxo.k.
Store
calibration
no; newyes;
Slope is
displayed
min. 25% (3%)
max. 500%
100%
CALIBRAT
Cl
2
/ ClO
2
ALARM
Select contact type
=
Latch = latching c.
Momen momentary c.
Select unit of alarm
delay
smin;
Define
error current
2.4 mA22 mA;
Select error number
1 ... 2551
Enable alarm
contact
noyes;
Alarm delay
0 ... 2000 min (s)
(dep. on F2)
0 min (s)
Feedforward control
to PID cont.
lin = linearOff;
Meas. value display
Temperature reading in °F
Meas. value display
no temp. display
Meas. value display
Sensor current in nA
Edit:
Code 22
Read:
any code
Edit:
Code 22
Read:
any code
Select meas. unit for
2nd current output
; mg/l; ppm; ppb; Contr°C
Zero calibration
yes
(only if A1 = 120)
no;
Calibration status is
displayed
Exxxo.k.
Store calibration
result
no; newyes;
CALIBRATION
zero
(CCS120)
Operating matrix versions EK and ES
A0002633-EN
Liquisys M CCM223/253 Appendix
Endress+Hauser 121
Z7
O336O335
O334
F9F8F7
Feedforward control
gain = 1 at
0 ... 100%50%
Enter y value (current)
0 ... 20.00 mA4.00 mA
Table status o.k.
noyes;
Enable error current
error just entered
yes
for
no;
Automatic start
of cleaning function
yesno;
Select “next error”
or return to menu
<---R
next = next error
Enter x value (meas. val.)
0 ... 20 (5) mg/l
0 ... 50 °C
0.00;
0 °C;
A7
Enter meas.
value damping
(no damping)
1 ... 60
1
A0002634-EN
Appendix Liquisys M CCM223/253
122 Endress+Hauser
R263
P114
R283
R243
R233
R213
R273
R264
P115
R284
R244
R234
R214
R2(7)
R2(6)
P111
R2(8)
R2(4)
R2(3)
R2(1)
R271
R261
P112
R281
R241
R231
R211
R262
P113
R282
R242
R232
R212
P1(1)
R1
P
R
R272
E141
E131
E121
S2
E142
E132
E122
S1
E1(4)
E1(3)
E1(2)
S S4 S5S3
E143 E144
E133 E134
E123 E124
E113 E114
E111 E112E1(1)
I1
E
I
CHECK
RELAY
Select alarm threshold
monitoring
Low; High
LoHi; Lo!; Hi!; LoHi!
Off;
Select contact to
be configured
Rel2; Rel3; Rel4Rel1;
Select start pulse
i+ext = internal + external
ext = external i+stp = int. w. suppression by ext.
int = internal
Define rinse time
0 ... 999 s30 s
Define pause time
1 ... 7200 min
360 min
Define minimum
pause time
1 ... 3600 min
120 min
Set lower
alarm threshold
0 ... 19.9 (4.9) mg/l
0.00 mg/l
Enter setpoint
0 ... 20 (5) mg/l
0.5 (0.1) mg/l
Enter control
gain K
p
0.01 ... 100.001.00
Enter integral action time
T
n
(0.0 = no I comp.)
0.0 ... 999.9 min0.0 min
Enter integral action time
T
n
(0.0 = no I comp.)
0.0 ... 999.9 min0.0 min
Enter control
gain K
p
0.01 ... 100.001.00
Enter setpoint
0 ... 20 (5) mg/l
0.5 (0.1) mg/l
Enter switch-on
temperature
0 ... 50 °C50 °C
Enter switch-off
temperature
0 ... 50 °C50 °C
Set pick-up
delay
0 ... 2000 s0 s
Set pick-up
delay
0 ... 2000 s0 s
Select switch-on point
of contact
0 ... 20 (5) mg/l
20 (5) mg/l
Select switch-off point
of contact
0 ... 20 (5) mg/l
20 (5) mg/l
Set upper
alarm threshold
0.1 ... 20 (5) mg/l
20.00 (5.00) mg/l
Enter pre-rinse time
0 ... 999 s20 s
Chlorine / ClO2
Switch function R2(7)
on or off
OnOff;
Clean =
Chemoclean
(only with Rel3 and Rel4)
Switch function R2(6)
on or off
OnOff;
Timer
Switch function R2(8)
on or off
OnOff;
3-point step controller
Cl2 / ClO2
(only with Rel3 and Rel4)
Switch function R2(4)
on or off
On; Basic; PID+BOff;
PID controller
Cl2 / ClO2
Switch function R2(3)
on or off
On; Basic; PID+BOff;
LC °C =
Limit contactor
T
Switch contact R2(1)
on or off
OnOff;
LC PV =
limit contactor
Cl2 / ClO2
Alarm delay
0 ... 2000 min (s)
(dep. on F2)
0 min (s)
SERVICE
E+H SERVICE
INTERFACE
Module software
SW Version
Hardware version
HW Version
Serial number
is displayed
Module identification
is displayed
Module
is displayed
identification
Module
is displayed
identification
Module
is displayed
identification
Serial number
is displayed
Serial number
is displayed
Serial number
is displayed
Hardware version
HW Version
Hardware version
HW Version
Hardware version
HW Version
Module software
SW Version
Module software
SW Version
Instrument software
SW Version
Enter address
HART: ... 15 or
PROFIBUS: 1 ...
0
126
Rel (= relay)
Main (= mainboard)
Trans (= transmitter)
Contr (= controller)
Manual Hold
OnOff;
Enter Hold
0 ... 999 s
dwell time
10 s
Enter SW upgrade
release code (Plus pack.)
0 ... 99990
Select language
GER; FRA;
ITA; NEL; ESP
ENG;
Configure Hold
CAL = with Cal.
Setup = for param. no
S+C = for param. + cal.
= no Hold
Select process
monitoring
AC; CC; AC CC
AC!; CC!; ACCC!
Off;
I2
Tag description
@@@@@@@@
A0002635-EN
Liquisys M CCM223/253 Appendix
Endress+Hauser 123
R2410
R2411
R285 R286
R235 R237R236
R245 R246
R276
P118
R287
R247
R274 R275 R277
R278 R279
R248
R249
P117
R216
R216
P116
R215 R217
S8S7S6 S9 S10
Enter deriv. action time
T
v
(0.0 = no D comp.)
0.0 ... 999.9 min0.0 min
Set
limit value
0 ... 20 (5) mg/l
0.5 (0.1) mg/l
Set max. perm. period of
upper limit exceeding
0 ... 2000 min120 min
Set max. perm. period of
lower limit exceeding
0 ... 2000 min60 min
Define period between
cleaning cycles
(pause time)
1 ... 7200 min
two
360 min
Define min.
pause time
1 ... R2 7 min120 min 7
Number of cleaning
cycles without
cleaning agent
0 ... 90
Enter cleaning
time
0 ... 999 s10 s
Enter post-rinse time
0 ... 999 s20 s
Define repeat
times
0 ... 50
Chemoclean: assigns 2 contacts,
only permitted for contacts 3+4
3-p. step contr.: assigns 2 contacts,
only permitted for contacts 3+4
Enter
max. pulse frequency
60 ... 180 1/min
120 1/min
Enter
pulse period
0.5 ... 999.9 s10.0 s
Select
freq = pulse frequency
curr = current output 2
len = pulse length
Select
control characteristic
dirinv;
Enter min. switch-on
time t
0.1 ... 5.0 s
ON
0.3 s
Enter min switch-on
time t
0.1 ... 5.0 s
ON
0.3 s
Motor run time
10 ... 999 s60 s
Neutral zone
0 ... 40%10%
Set drop-out
delay
0 ... 2000 s0 s
Set alarm
threshold (as abs. value)
0 ... 50 °C50 °C
Display LC status
; MINMAX
Display LC status
; MINMAX
Set alarm
threshold (as abs. value)
0 ... 20 (5) mg/l
20 (5) mg/l
Set dropout
delay
0 ... 2000 s0 s
Enter SW upgrade
release code Chemocl.
0 ... 99990
Reset instrument
sens; factoryno;
Start instrument test
displayno;
Order number
is displayed
Serial number
is displayed
Enter basic load
0 ... 40%0%
A0002636-EN
Appendix Liquisys M CCM223/253
124 Endress+Hauser
C
A1
A4A3
A5 A6
A
B
Z Z4
O332
B5
Z5
O333
B1
Z1
B2*
Z2
O3(3)
B3
Z3
O331
B4
O3(2)
O321
O O1 O2 O3(1) O311 O312 O313
C35
C25
C15
C26
C32
C22
C12
C33
C23
C13
C34
C24
C14
C31
C21
C11
Z6
A2
C15
C14 C15
CURRENT INPUT
SETUP 2
SETUP 1
CURRENT OUTPUT
Enter value of ORP
buffer
0 ... 1500 mV
Buffer value of last cal.
Meas. value display
ORP (dep. on B1)pH;
1st error is displayed
(if present)
Meas. value display
Temperature display in °F
Meas. value display
pH signal in mV
Other errors are
displayed
(up to max. 10 errors)
Meas. value display
No temp. display
Enter pH value
of first buffer solution
pH 3.50 ... 9.50
Buffer value of last cal.
Controller switch-off
by sample stream
INSOff;
Controller switch-off
by current input
InputOff;
Select meas. parameter
for 2nd current output
pH; ORPmV; Contr°C;
Select current range
0–20 mA4–20 mA;
lin = linear
pH compensation
Manu; AutoOff;
Enter pH value
of second buffer solution
pH 3.50 ... 9.50
Buffer value of last cal.
Slope is
displayed
38.00 ... 65.00 mV/pH
59.16 mV/pH
Switch-off direction
for current input
HighLow;
Zero calibration
yes
(only if A1 = 963)
no;
Enter calibration
temperature
–10 ... +60 °C25.0 °C
Select sensor
140; 141; 240; 241;
963; 120
Select current output
Output2Output1;
Select operating mode
pH; ORP mVOff;
Enter DPD
calibration value
Value of last cal.
Calibrating
Adopt if stable
±1 mV (> 10 s)
Calibrating
Adopt if stable
pH ±0.05 (> 10 s)
Delay for contr.
sw.-off by sample stream
0 ... 2000 s0 s
Delay for controller
sw.-off current input
0 ... 2000 s0 s
Tab = Table
sim = simulation
Manual
pH compensation
pH 4.00 ... 9.00
last comp. value
Delay for contr.
sw.-on by sample stream
0 ... 2000 s0 s
Delay for controller
sw.-on current input
0 ... 2000 s0 s
Enter simulation
value
0 ... 22.0 mA
current value
Select table
options
editread
Enter number of
table pairs
1 ... 101
Select table
pairs
1 ... No. of table pairs
asign
1
Enter correct
process temperature
0 ... 50 °C
current meas. value
Calibrating
Adopt if stable
pH ±0.05 (> 10 s)
Select
digital input 1
Clean Trig.ext.Hold
Switch-off limit
for current input
0 ... 100%50%
Enter temperature
difference (offset)
–5.0 ... + 5.0 °C
current offset
Calibration status is
displayed
Exxxo.k.
Calibration status is
displayed
Exxxo.k.
Enter calibration
results
no; newyes;
Store calibration
result
no; newyes;
Zero point is
displayed
–100 ... +100 mV
Slope is
displayed
min. 25% (3%)
max. 500%
100%
CALIBRATION
ORP mV
(dep. on B1)
CALIBRATION
pH
(dep. on B1)
MEAS. VALUE
DISPLAY
TEMPERATURE
DISPLAY
with
in °C
CALIBRATION
Cl
2
/ ClO
2
Feedforward control
to PID controller
lin = linearOff;
Meas. value display
Sensor current in nA
Edit:
Code 22
Read:
any code
Edit:
Code 22
Read:
any code
Display unit
ppm; ppbmg/l;
Enter 0/4-mA value
0.00 mg/l;
0.00 ppm
0 ppb;
pH 4.00;
0 mV;
0 °C;
0 ... 20 (5) mg/l
; 0 … 20 ppm
0 … 20000 ppb
pH 4 ... 9
0 ... 1500 mV
0 ... 50 °C
Enter 20-mA value
2.0 (0.5);
2.0 ppm;
2000 ppb;
pH 9.00;
1000 mV;
50 °C;
0 ... 20 (5) mg/l
0 … 20 ppm
0 … 20000 ppb
pH 4 ... 9
0 ... 1500 mV
0 ... 50 °C
* field B2 not available for CCS240/241
CALIBRATION
zero
(CCS120)
Zero calibration
yes
(only if A1 = 120)
no;
Calibration status is
displayed
Exxxo.k.
Store calibration
result
no; newyes;
Operating matrix version EP
A0002637-EN
Liquisys M CCM223/253 Appendix
Endress+Hauser 125
Store calibration
results
no; newyes;
Calibration status is
displayed
Exxxo.k.
Feedforward control
gain = 1 at
0 ... 100%50%
Zero point is
displayed
pH 5.00 ... 9.00
pH 7.00
Enter x value (meas. val.)
0 ... 20 (5) mg/l
pH 4 ... 9
0 ... 1500 mV
0 ... 50 °C
0.,00;
pH 4.00;
0 mV;
0 °C;
Enter y value (current)
0 ... 20.00 mA4.00 mA
Table status o.k.
noyes;
Only LCD switchover!
Meas. value display
Current input in %
Meas. value display
Current input in mA
A7
Enter meas.
value damping
(no damping)
1 ... 60
1
Z7
O336
O334
O335
C28 C29
C27
Only LCD switchover!
A0002638-EN
Appendix Liquisys M CCM223/253
126 Endress+Hauser
F5 F6
P124
P124
R263
P114
R283
R253
R243
R233
R223
R223
R213
P125
R273
P125
R264
P115
R284
R254
R244
R234
R224
R224
R214
F2
P121
R2(7)
P121
R2(6)
P111
R2(8)
R2(5)
R2(4)
R2(3)
R2(2)
R2(2)
R2(1)
F3
P122
R271
P122
R261
P112
R281
R251
R241
R231
R221
R221
R211
F4
P123
P123
R262
P113
R282
R252
R242
R232
R222
R222
R212
F1
P1(2)
P1(2)
P1(1)
R1
F
P
R
R272
ALARM
CHECK
RELAY
Select contact type
Momen = momentar c
Latch = latching c.
y .
Select alarm threshold
monitoring
Low!; High!; LoHi!
Low; High; Lo HiOff;
Select alarm threshold
monitoring
Low!; High!; LoHi!
Low; High; Lo HiOff;
Select alarm threshold
monitoring
Low; High
Lo Hi; Low! High!; LoHi!
Off;
;
Select contact to
be configured
Rel2; Rel3; Rel4Rel1;
Set lower
alarm threshold
0 ... 1490 mV0 mV
Select start pulse
i+ext = internal + external
ext = external i+stp = int. w. suppression of ext.
int = internal
Set lower
alarm threshold
pH 4 ... 8.9pH 4.00
Define rinse time
0 ... 999 s30 s
Define pause time
1 ... 7200 min
360 min
Define min. pause
time
1 ... 3600 min
120 min
Set upper
alarm threshold
pH 4.1 ... 9pH 9.00
Enter control
gain K
p
0.01 ... 100.001.00
Enter integral action time
T
n
(0.0 = no I comp.)
0.0 ... 999.9 min0.0 min
Enter integral action time
T
n
(0.0 = no I comp.)
0.0 ... 999.9 min0.0 min
Enter integral action time
T
n
(0.0 = no I comp.)
0.0 ... 999.9 min0.0 min
Enter control
gain K
p
0.01 ... 100.001.00
Enter control
gain K
p
0.01 ... 100.001.00
Enter setpoint
pH 4 ... 9pH 7.20
Set switch-on
temperature
0 ... 50 °C50 °C
Set switch-off
temperature
0 ... 50 °C50 °C
Set pick-up
delay
0 ... 2000 s0 s
Set pick-up
delay
0 ... 2000 s0 s
Set pick-up
delay
0 ... 2000 s0 s
Set pick-up
delay
0 ... 2000 s0 s
Select contact
switch-on point
pH 4 ... 9
pH 9
Select contact
switch-off point
pH 4 ... 9
pH 9
Select contact
switch-on point
0 ... 1500 mV
1500 mV
Select contact
switch-off point
0 ... 1500 mV
1500 mV
Set upper
alarm threshold
10 ... 1500 mV1500 mV
Select process
monitoring
AC; AC!Off;
Enter pre-rinse time
0 ... 999 s20 s
Select process
monitoring
AC; CC; AC CCOff;
AC!; CC!; ACCC!
Select process
monitoring
AC; CC; AC CC
AC!; CC!; ACCC!
Off;
ORP mV
(dep. on B1)
pH
(dep. on B1)
Chlorine / ClO2
Select unit for
alarm delay
smin;
Alarm delay
0 ... 2000 min (s)
(depending on F2)
0 min (s)
Switch function R2(7)
on or off
OnOff;
Clean =
Chemoclean
(only with Rel3 and Rel4)
Switch function R2(6)
on or off
OnOff;
Timer
Switch function R2(8)
on or off
OnOff;
3-point step controller
Cl2 / ClO2
(only with Rel3 and Rel4)
Switch function R2(5)
on or off
On; Basic; PID+BOff;
PID controller
pH
Switch function R2(4)
on or off
On; Basic; PID+BOff;
PID controller
Cl2 / ClO2
Switch function R2(3)
on or off
OnOff;
LC °C =
Limit contactor
T
Switch function R2(2)
on or off
OnOff;
LCORP =
Limit contactor
ORP
(dep. on B1)
LC pH =
Limit contactor
pH
(dep. on B1)
Switch function R2(2)
on or off
OnOff;
Switch function R2(1)
on or off
OnOff;
LC PV =
Limit contactor
Cl2 / ClO2
Alarm delay
0 ... 2000 min (s)
(depending on F2)
0 min (s)
Alarm delay
0 ... 2000 min (s)
(depending on F2)
0 min (s)
Define
error current
2.4 mA22 mA;
Select error number
1 ... 2551
Enable alarm
contact
noyes;
Alarm delay
0 ... 2000 min (s)
(depending on F2)
0 min (s)
Enter setpoint
0.5 (0.1) mg/l;
0.5 ppm
500 ppb;
0 ... 20 (5) mg/l
; 0 20 ppm
0 20000 ppb
Set lower
alarm threshold
0.00 mg/l;
0.00 ppm
0 ppb;
0 ... 20 mg/l
; 0 20 ppm
0 20000 ppb
Set upper
alarm threshold
20.00 mg/l;
20.00 ppm
20000 ppb;
0 ... 20 mg/l
; 0 20 ppm
0 20000 ppb
Enter setpoint
0.5 (0.1) mg/l;
0.5 ppm
500 ppb;
0 ... 20 (5) mg/l
; 0 20 ppm
0 20000 ppb
Select contact
switch-on point
20 (0.5) mg/l;
20 ppm
20000 ppb;
0 ... 20 (5) mg/l
; 0 20 ppm
0 20000 ppb
Select contact
switch-off point
20 (0.5) mg/l;
20 ppm
20000 ppb;
0 ... 20 (5) mg/l
; 0 20 ppm
0 20000 ppb
A0002639-EN
Liquisys M CCM223/253 Appendix
Endress+Hauser 127
R2510
R2410
R285 R286
R225 R226
R225
R226
R235 R236
R245 R246
R255 R256
F9
R276
P128
P118
R287
R257
R247
R274 R275 R277 R278 R279
P126
R258
R248
R259
R249
F8
P127
P117
R216
F7
P116
R215
Enable error current for
error just selected
yesno;
Automatic start
of clean function
yesno;
Select “next error”
or return to menu
<---R
next = next error
Set max. perm. period
for lower alarm threshold
0 ... 2000 min60 min
Set max. perm. period
for upper alarm threshold
0 ... 2000 min120 min
Set limit
value
pH 4 ... 9pH 7.20
Set max. perm. period
for lower limit exceeding
0 ... 2000 min120 min
Set max. perm. period
for lower limit exceeding
0 ... 2000 min60 min
Define period between
two cleaning cycles
(pause time)
1 ... 7200 min360 min
Define minimum
pause time
1 ... R277 min120 min
Number of cleaning
cycles without
cleaning agent
0 ... 90
Enter cleaning
time
0 ... 999 s10 s
Enter post-rinse time
0 ... 999 s20 s
Define repeat
cycles
0 ... 50
Chemoclean: assigns 2 contacts,
only permitted for contacts 3 (+4)
3-p. step controller: assigns 2
only permitted for contacts 3+4
con-
tacts,
Select control
characteristic
; invdir
Select
freq = pulse frequency
curr = current output 2
len = pulse length
Select
freq = pulse frequency
curr = current output 2
len = pulse length
Enter
pulse period
0.5 ... 999.9 s10.0 s
Enter max.
pulse frequency
60 ... 180 1/min
120 1/min
Enter max.
pulse frequency
60 ... 180 1/min
120 1/min
Enter
pulse period
0.5 ... 999.9 s10.0 s
Select control
characteristic
dirinv;
Enter min. switch-on
t
0.1 ... 5.0 s
time
ON
0.3 s
Enter min. switch-on
time t
0.1 ... 5.0 s
ON
0.3 s
Enter min. switch-on
time t
0.1 ... 5.0 s
ON
0.3 s
Motor run time
10 ... 999 s60 s
Neutral zone
0 ... 40%10%
Enter deriv. action time
T
v
(0.0 = no D comp.)
0.0 ... 999.9 min0.0 min
Enter deriv. action time
T
v
(0.0 = no D comp.)
0.0 ... 999.9 min0.0 min
Set drop-out
delay
0 ... 2000 s0 s
Set alarm threshold
0 ... 50 °C50 °C
Set alarm threshold
pH 0 ... 9pH 9.00
Set alarm threshold
0 ... 1500 mV1500 mV
Set drop-out
delay
0 ... 2000 s0 s
Set drop-out
delay
0 ... 2000 s0 s
Set drop-out
delay
0 ... 2000 s0 s
R2511
Enter basic load
0 ... 40%0%
R2411
Enter basic load
0 ... 40%0%
R237
R227
R227
R217
Display of LC status
; MINMAX
Display of LC status
; MINMAX
Display of LC status
; MINMAX
Display of LC status
; MINMAX
Set limit value
0.5 (0.1) mg/l;
0.5 ppm
500 ppb;
0 ... 20 (5) mg/l
; 0 … 20 ppm
0 … 20000 ppb
Set alarm threshold
20 (5) mg/l;
20 ppm
20000 ppb;
0 ... 20 (5) mg/l
; 0 … 20 ppm
0 … 20000 ppb
A0002640-EN
Appendix Liquisys M CCM223/253
128 Endress+Hauser
S4 S5
E141
E131
E121
E111
S2
E142
E132
E122
E112
S3
E143 E144
E133 E134
E123 E124
E113 E114
S1
E1(4)
E1(3)
E1(2)
E1(1)
I1
S
E
I
SERVICE
E+H SERVICE
INTERFACE
Select language
GER; FRA;
ITA; NEL; ESP
ENG;
Module software
SW Version
Hardware version
HW Version
Serial number
is displayed
Module identification
is displayed
Module
is displayed
identification
Module
is displayed
identification
Module
is displayed
identification
Serial number
is displayed
Serial number
is displayed
Serial number
is displayed
Hardware version
HW Version
Hardware version
HW Version
Hardware version
HW Version
Module software
SW Version
Module software
SW Version
Instrument software
SW Version
Enter address
HART: ... 15 or
PROFIBUS: 1 ...
0
126
Rel (= relay)
Main (= mainboard)
Trans (= transmitter)
Contr (= controller)
Manual Hold
OnOff;
Enter Hold
dwell time
0 ... 999 s10 s
Enter SW upgrade
release code (Plus pack.)
0 ... 99990
Configure Hold
CAL = for Cal.
Setup = for param. no
S+C = for param. + cal.
= no Hold
I2
Tag description
@@@@@@@@
A0002641-EN
Liquisys M CCM223/253 Appendix
Endress+Hauser 129
S8S7S6 S9 S10
Control SW upgrade
release code Chemocl.
0 ... 99990
Reset instrument
sens; factoryno;
Start instrument test
displayno;
Order number
is displayed
Serial number
is displayed
A0002642-EN
Index Liquisys M CCM223/253
130 Endress+Hauser
Index
A
Access codes ............................... 36
Accessories ...............................109
Alarm ....................................55
Alarm contact .............................. 29
Approvals ................................. 10
Automatic mode ............................ 35
C
Calibration ................................ 81
Central module replacement .................. 107
Certificates ................................ 10
Check .................................... 56
Cleaning
Sensors ................................ 96
Transmitter ............................. 95
Commissioning ............................. 38
Communication .............................80
Connecting cables ........................... 98
Current input .............................. 47
Current outputs .............................51
D
Designated use .............................. 7
Device configuration ......................... 42
Device-specific errors .........................93
Diagnostics ................................ 85
Disassembling
Field device ............................ 104
Panel-mounted device .................... 101
Display ................................... 30
Disposal ................................. 108
E
E+H Service ................................79
Electrical connection ......................... 19
Version 1 ...............................19
Version 2 ...............................21
Environment ..............................117
F
Feedforward control ......................... 48
H
Hold function .............................. 37
I
Incoming acceptance .......................... 9
Input ................................... 113
Installation ................................ 11
Installation conditions ........................14
Installation instructions .......................16
Interfaces ................................. 80
J
Junction boxes ..............................98
K
Key functions .............................. 32
L
Local operation ............................. 35
M
Maintenance ...............................95
Assembly ...............................97
Sensor ................................. 97
Maintenance of the entire measuring point ........ 95
Manual mode .............................. 35
Measuring system ...........................12
Mechanical construction ..................... 118
Menu structure ............................. 37
N
Nameplate ................................ 10
O
Operating concept ...........................36
Operating elements ..........................32
Operating modes ............................36
Operation ................................. 30
Output .................................. 113
P
P(ID) controller ............................. 62
Performance characteristics ...................117
Post mounting ..............................16
Post-connection check ........................29
Post-installation check ....................... 18
Power supply ............................. 116
Process-specific errors ........................89
Product identification ......................... 9
Q
Quick Setup ................................40
R
Relay configuration .......................... 60
Repair ...................................101
Replacing the central module ..................107
Return .................................. 107
S
Safety instructions ............................7
Scope of delivery ............................. 9
SCS monitoring functions ......................57
Sensor connection ...........................24
Service ................................... 77
Setup 1 ................................... 42
Setup 2 ................................... 44
Spare parts ............................... 101
Switching on ...............................38
Symbols ................................... 5
System error messages ....................... 85
Liquisys M CCM223/253 Index
Endress+Hauser 131
T
Technical data .............................113
Test
Chlorine sensors ..........................98
Flow monitoring ..........................99
pH/ORP measurement ..................... 99
Temperature measurement ................. 99
Test and simulation ..........................98
Three-point step controller ................. 28, 67
Trouble shooting instructions .................. 85
Troubleshooting ............................ 85
U
Use .......................................7
W
Wall mounting ............................. 16
Warnings .................................. 5
Wiring ................................... 19
www.addresses.endress.com
*71300499*
71300499